Operation
8.4 Initializing the actuator
To achieve correct position feedback, the actuator must be initialized. This is also necessary
after changing any settings at the actuator.
WARNING
!
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
NOTICE
!
The process is disturbed by the movement of the actuator stem.
Do not perform the initialization while the process is running. First isolate the plant by closing
the shut-off valves.
Start initialization
1. Place the function switch into the required position.
2. Switch the function switch briefly from its position to the other position and back again.
The red LED indicates that initialization is in progress:
On
Off
2

8.5 Serial interface

8.5.1

TROVIS-VIEW

The actuator is configured with the TROVIS-VIEW software. In this case, the serial interface
on the actuator is used to connect the actuator to the computer.
Î Refer to section 9 for more details on configuration and operation using TROVIS-VIEW.
8.5.2

Memory pen

A memory pen can also be inserted at the serial interface.
Î Refer to section 10.2 for more details on the memory pen.
38
4
6
8
10
Time [s]
EB 5824-2 EN