Position Feedback Signal - Samson 5824 Mounting And Operating Instructions

Electric actuators, with / without fail-safe action, version with positioner
Table of Contents

Advertisement

Set input signal: Settings\Inputs and outputs\Input signal
Input signal
Lower range value
Upper range value
9.5.2

Position feedback signal

The position feedback indicates the position of the actuator stem.
The span of the position feedback signal is adjusted over the lower and upper range value
parameters.
Set position feedback signal: Settings\Inputs and outputs\Position feedback signal
Position feedback signal
Lower range value
Upper range value
EB 5824-2 EN
Configuration and operation using TROVIS-VIEW
WE
0.0 V or 0.0 mA
10.0 V or 20.0 mA
WE
0.0 V
10.0 V
Adjustment range
0.0 to 7.5 V or 0.0 to 15.0 mA
2.5 to 10.0 V or 5.0 to 20.0 mA
Adjustment range
0.0 V to 10.0 V
0.0 V to 10.0 V
45