Additional functions
6 Additional functions
Devices in 24 V version can be fitted with
limit contacts as additional function.
The limit contacts (6 in Fig. 1 on page 12)
can be used either as make or break con-
tacts.
6.1 Adjusting the limit contacts
DANGER
!
Risk of electric shock from exposed live
parts.
Do not touch live parts on adjusting the limit
contacts.
Terminal assignment (Fig. 9):
− Terminals 41, 44, 42:
Î Bottom cam disk, adjuster 7.1
− Terminals 51, 54, 52:
Î Top cam disk, adjuster 7.2
1. Unscrew front cover.
2. Move the actuator to the travel position
at which switching point is to be activat-
ed.
3. Use a 4 mm Allen key to turn the adjust-
ers (7.1 or 7.2 in Fig. 1 on page 12)
up to the point where the contact is trig-
gered. The angle of rotation of the cam
disks is limited. Therefore, use preferably
the top adjuster (7.1) for the upper travel
range and the bottom adjuster (7.2) for
the lower travel range.