Eaton Powerware 9395 Plus 1 Installation And Operation Manual
Eaton Powerware 9395 Plus 1 Installation And Operation Manual

Eaton Powerware 9395 Plus 1 Installation And Operation Manual

225–275 kva powerware series
Hide thumbs Also See for Powerware 9395 Plus 1:
Table of Contents

Advertisement

Quick Links

Powerware Series
®
Eaton 9395 Plus 1 UPS
225–275 kVA
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Powerware 9395 Plus 1

  • Page 1 Powerware Series ® Eaton 9395 Plus 1 UPS 225–275 kVA Installation and Operation Manual...
  • Page 3 Powerware Series ® Eaton 9395 Plus 1 UPS 225–275 kVA Installation and Operation Manual...
  • Page 4: Important Safety Instructions

    Schneider Electric. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ECopyright 2008-2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 5: Table Of Contents

    ..............164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 6 ................. . . 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 7 ................7-42 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 8 ................164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 9 ..............Figure 3‐8. Eaton 9395 Plus 1 UPS (225–275 kVA) Cabinet as Shipped on Pallet .
  • Page 10 ................164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 11: Introduction

    Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 12: Figure 1-1. Eaton 9395 Plus 1 Ups (225-275 Kva) Cabinet

    INTRODUCTION Figure 1‐1. Eaton 9395 Plus 1 UPS (225–275 kVA) Cabinet 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 13: Control Panel

    The Maintenance Bypass Module (MBM) enables power to completely bypass and isolate the UPS so that the UPS can be safely serviced or replaced without interrupting power to critical systems. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 14: Sync Control

    1.2.5 Separate Rectifier Input The Eaton 9395 225–275 kVA Plus 1 UPS can be supplied with separate rectifier inputs for each UPM. Separate inputs provide increased flexibility and reliability by allowing multiple input sources to supply the UPS. Input circuit breaker CB1 is not installed with this configuration.
  • Page 15: Inherent Redundancy

    1.2.7 Inherent Redundancy To deliver greater reliability, the Eaton 9395 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
  • Page 16: Monitoring And Communication

    UPMs in distributed bypass and parallel systems must use a separate battery system. A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not required for normal operation. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 17: Basic System Configurations

    275 kVA ISBM, two UPM, Continuous Static Switch (CSS) Using This Manual This manual describes how to install and operate the Eaton 9395 Plus 1 UPS (225–275 kVA) cabinet. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 7.3.25 on page 7-28).
  • Page 18: Conventions Used In This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 19: For More Information

    Detailed illustrations of the cabinet, including dimension and connection point drawings. Refer to the Eaton 9390 and 9395 Sync Control Installation and Operation Manual for the following additional information: Installation instructions, including site preparation, planning for installation, and wiring and safety information.
  • Page 20 INTRODUCTION This page intentionally left blank. 1-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 21: Safety Warnings

    Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit. Do not install or operate the UPS system close to gas or electric heat sources. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 22 Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 23 Section I Installation 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 24 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 25: Ups Installation Plan And Unpacking

    Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 26 95%, noncondensing C A U T I O N If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supercede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
  • Page 27: Figure 3-1. Ups Cabinet Dimensions (Front View)

    Dimensions are in millimeters [inches]. Figure 3‐1. UPS Cabinet Dimensions (Front View) Dimensions are in millimeters [inches]. Figure 3‐2. UPS Cabinet Dimensions (Right Side View) 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 28: Figure 3-3. Ups Cabinet Dimensions (Top View)

    Dimensions are in millimeters [inches]. Figure 3‐4. UPS Cabinet Dimensions (Bottom View) Front Dimensions are in millimeters [inches]. Figure 3‐5. UPS Cabinet Dimensions (Bottom View with Mounting Brackets) 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 29: Figure 3-6. Ups Cabinet Center Of Gravity

    1.57 [0.40] Needed to remove key Front View 1/2” Knockout Pattern (Typical 5 Sides) Dimensions are in millimeters [inches]. Figure 3‐7. Remote EPO Switch Dimensions 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 30: Ups System Power Wiring Preparation

    With this type of supply source, there is no capability to provide an output neutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 31 For external wiring requirements, including the minimum AWG size of external wiring, see Table 3‐4 for installations using a common battery system or Table 3‐5 for installations using a separate battery system. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 32 UPS INSTALLATION PLAN AND UNPACKING Table 3‐4. Input/Output Ratings and External Wiring Requirements for the Eaton 9395-275/225 and 9395-275/275 – Common Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400 480/480 AC Input to UPS Rectifier (0.98 Minimum pF)
  • Page 33 UPS INSTALLATION PLAN AND UNPACKING Table 3‐5. Input/Output Ratings and External Wiring Requirements for the Eaton 9395-275/225 and 9395-275/275 – Separate Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400 480/480 AC Input to UPS Rectifier (0.98 Minimum pF)
  • Page 34 (3) Phases, (1) Ground Minimum Conductor Size AWG or kcmil Number per Phase (each) NOTE Callout letter maps to Figure 6‐7 on page 6-10. 3-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 35 Figure 4‐6 on page 4-11 and Figure 4‐7 on page 4-12 show the location of the power cable terminals inside the UPS. Table 3‐7. UPS Cabinet Power Cable Terminations for the Eaton 9395-275/225 and 9395-275/275 Tightening Torque Terminal Function...
  • Page 36 Manual Hydraulic Crimp Tool 14 Ton Thomas & Betts TBM14M Die Set Thomas & Betts 15506 Table 3‐10. Separate Rectifier Input UPM Power Cable Terminations for the Eaton 9395-275/225, and 9395-275/275 Tightening Torque Terminal Function Terminal Function Size of Pressure Termination Type Screw...
  • Page 37 NOTE Select conduit taking into consideration the DC input wire sizes listed in Table 3‐4 on page 3-8 or Table 3‐5 on page 3-9, the DC terminations listed in Table 3‐7 on page 3-11, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT). 3-13 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 38 AC output to critical load shown in Table 3‐4 on page 3-8 or Table 3‐5 on page 3-9. The recommended line‐to‐line load unbalance is 50% or less. 3-14 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 39 The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current. 3-15 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 40: Ups System Interface Wiring Preparation

    Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28 Vdc. Alarm relay wiring should be a minimum of 22 AWG. 3-16 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 41: Distributed Bypass Power Wiring Preparation

    With dual auxiliary MOBs, one UPM can be bypassed while the remaining UPMs support the load as long as the remaining UPMs have the capacity to do so. 3-17 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 42: Inspecting And Unpacking The Ups Cabinet

    Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3‐1 on page 3-2 for cabinet weight).
  • Page 43: Figure 3-8. Eaton 9395 Plus 1 Ups (225-275 Kva) Cabinet As Shipped On Pallet

    NOTE While waiting for installation, protect the unpacked cabinet from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. Figure 3‐8. Eaton 9395 Plus 1 UPS (225–275 kVA) Cabinet as Shipped on Pallet 3-19 164201710 Rev 2 www.eaton.com\powerquality...
  • Page 44 UPS INSTALLATION PLAN AND UNPACKING This page intentionally left blank. 3-20 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 45: Ups System Installation

    End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 46 Step 12. 12. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.4; otherwise, proceed to paragraph 4.5. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 47: Figure 4-1. Removing The Left Side Shipping Bracket

    UPS SYSTEM INSTALLATION UPM Removable Front Panels Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Figure 4‐1. Removing the Left Side Shipping Bracket 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 48: Figure 4-2. Removing The Right Side Shipping Bracket

    Center Front Panel Removable Left Front Panel Pallet Shipping Bracket Bolts Right Side Shipping Bracket Shipping Bracket Bolts Figure 4‐2. Removing the Right Side Shipping Bracket 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 49: Battery System Installation

    UPS SYSTEM INSTALLATION Battery System Installation If installing an Eaton battery cabinet, refer to the Eaton 9395 Integrated Battery Cabinet (Model IBC-L) Installation Manual, listed in paragraph 1.8 on page 1-9. If installing a customer-supplied battery system, install the battery system according to the battery and battery system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
  • Page 50: Hole Barrel Lug Terminations To Bus Bar Installation

    Conical Washer Flat Washer Bus Bar Flat Washer Bolt Head Double Lug Installation Figure 4‐3. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 51: External Power Wiring Installation

    UPS cabinet. See paragraph 3.2.2 on page 3-6 for wiring and termination requirements. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 52: Figure 4-4. Conduit And Wire Entry Locations

    Bottom Entry Conduit Landing for AC Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) Figure 4‐4. Conduit and Wire Entry Locations 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 53 See paragraph 3.2.2 on page 3-6 for wiring and termination requirements. 14. Proceed to paragraph 4.5.3. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 54: Figure 4-5. Distributed Bypass Wire Length

    NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%. Figure 4‐5. Distributed Bypass Wire Length 4-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 55: Figure 4-6. Ups Power Terminal Locations - Common Rectifier Feed

    (A, B, C) (See Figure 4‐7 for Detail AA.) ISBM UPM 1 UPM 2 Figure 4‐6. UPS Power Terminal Locations – Common Rectifier Feed 4-11 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 56: Figure 4-7. Ups Power Terminal Detail Aa - Common Rectifier Feed

    Alternate Ground Phase B (E7) UPS Bypass Terminal Bus Location Phase A (E6) Figure 4‐7. UPS Power Terminal Detail AA – Common Rectifier Feed 4-12 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 57: Figure 4-8. Ups Power Terminal Locations - Separate Rectifier Feed

    (A, B, C) (See Figure 4‐9 for detail AA.) ISBM UPM 1 UPM 2 Figure 4‐8. UPS Power Terminal Locations – Separate Rectifier Feed 4-13 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 58: Figure 4-9. Ups Power Terminal Detail Aa - Separate Rectifier Feed

    AC Input to Phase B (E2) UPM Rectifiers Phase C (E3) UPM 2 UPM 1 Figure 4‐10. UPM Rectifier Input Power Terminal Block Detail 4-14 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 59: Battery Power Wiring

    “Product Specifications,” for maximum battery charger currents. To install wiring to connections: If using an Eaton battery cabinet, proceed to Step 2; otherwise, proceed to Step 4. Route and connect the battery cables between the UPS and battery cabinet or battery disconnect according to the instructions in the Eaton 9395 Integrated Battery Cabinet (Model IBC-L) Installation Manual, listed in paragraph 1.8 on...
  • Page 60: Figure 4-11. Ups Power Terminal Detail Bb - Common Battery

    UPS SYSTEM INSTALLATION DC Input from Battery + (E4) DC Input from Battery – (E5) Figure 4‐11. UPS Power Terminal Detail BB – Common Battery 4-16 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 61: Installing Interface Connections

    Chapter 7, “UPS Operating Instructions,” for shutdown instructions. Unfasten the front door latch and swing the door open (see Figure 4‐2 on page 4-4). 4-17 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 62 16. If removed, reinstall the safety shield panel removed in Step 6. Secure with the retained hardware. 17. If removed, reinstall the left front panel removed in Step 5 and secure with the retained hardware. 4-18 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 63: Figure 4-13. Interface Terminal Locations

    (See Figure 4‐14 for Detail.) (See Figure 4‐19 on page 4-25 for detail.) (See Figure 4‐16 on page 4-22 for terminal assignments.) Figure 4‐13. Interface Terminal Locations 4-19 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 64 Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. 4-20 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 65: Figure 4-14. Interface Terminal Detail

    NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Figure 4‐15. Typical Alarm Relay Connection 4-21 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 66: Figure 4-16. Terminal Blocks Tb1, Tb2, And Tb3 Connector Assignments

    NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4‐16. Terminal Blocks TB1, TB2, and TB3 Connector Assignments 4-22 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 67: Tb1 Battery Interface Connections

    (see Figure 4‐4 on page 4-8). 10. Reinstall the interface entry plates and install the conduit. 11. If using an Eaton battery cabinet, proceed to Step 12; otherwise, proceed to Step 15. 12. Route the shunt trip and aux wiring from the battery cabinet or battery disconnect to the UPS cabinet.
  • Page 68: Figure 4-17. Typical Battery Interface Connection

    NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4‐18. Typical Battery Interface Connection – Separate Battery System 4-24 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 69: X-Slot Connections

    NOTE When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-9). To install wiring to connections: If not already installed, install the LAN and telephone drops.
  • Page 70: Installing A Repo Switch

    NOTE The REPO switch must be a normally-open or normally-closed latching‐type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
  • Page 71 Terminal Board TB1 in (Either Block) UPS Cabinet 3 NO TB1‐3 Twisted Wires (2) 7 lb in 14–22 AWG (0.8 Nm) 4 NO TB1‐4 (0.75–4.0 mm 4-27 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 72: Figure 4-21. Normally-Open Repo Switch Wiring

    Figure 4‐22 shows the wiring connections if the normally-closed REPO contacts are used, and Figure 4‐23 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. 4-28 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 73: Figure 4-22. Normally-Closed Repo Switch Wiring

    NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4‐23. Normally‐Closed and Normally‐Open REPO Switch Wiring 4-29 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 74: Installing Options And Accessories

    Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 75: Installation Checklist

    - Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) - The debris shields covering the UPS cabinet ventilation grills are removed. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-31 164201710 Rev 2 www.eaton.com\powerquality...
  • Page 76 - Pull-chain wiring between the UPS cabinets is properly installed. - Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-32 164201710 Rev 2 www.eaton.com\powerquality...
  • Page 77 UPS SYSTEM INSTALLATION Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ 4-33 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 78 UPS SYSTEM INSTALLATION This page intentionally left blank. 4-34 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 79: Installing An Optional Powerware Hot Sync Can Bridge Card

    UPS. See Figure 4‐13 on page 4-19 and Figure 4‐19 on page 4-25 for X-Slot communication bay locations. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 80 RIM II (see paragraph 5.4) SCM II (see paragraph 5.5) To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 5‐2 and Table 5‐1. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 81: Figure 5-2. Powerware Hot Sync Can Bridge Card Connections

    Normally‐open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN Input for parallel operation. Shield 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 82: Installing Distributed Bypass Control Wiring

    NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
  • Page 83: Figure 5-3. Distributed Bypass System Can And Pull-Chain Simplified Interface Wiring

    (If Installed) J3–8 (L) J3–8 (L) J3–8 (L) J3–8 (L) J3–9 (H) J3–9 (H) J3–9 (H) J3–9 (H) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 84: Figure 5-5. Distributed Bypass Pull-Chain Wiring Without Mobs

    TB2–1 (Pull Chain) (Pull Chain) (Pull Chain) (Pull Chain) TB2–2 TB2–2 TB2–2 TB2–2 (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 85: Figure 5-6. Distributed Bypass Pull-Chain Wiring With Mobs

    NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 86 MOB 2 Aux 2 Com MOB 2 Aux 2 Com MOB 3 Aux 2 Com Pull Chain MOB Common MOB 3 Aux 2 Com MOB 4 Aux 2 Com 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 87: Installing An Optional Remote Monitor Panel Ii

    11. If removed, reinstall the left front panel removed in paragraph 5.1, Step 4 and secure with the retained hardware. 12. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 88: Figure 5-7. Remote Monitor Panel Ii And Remote Monitor Panel Ii Terminal Locations

    0.9 (8) Use twisted pair J3–7 (TX) TB1–4 (RDX) 0.9 (8) TB3 Line 0.9 (8) TB3 Neutral 0.9 (8) Ground Terminal 2.7 (24) Maximum 5-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 89: Installing An Optional Relay Interface Module Ii

    INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 13. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass.
  • Page 90: Figure 5-9. J1, J2, J3, And J4 15-Pin D-Sub Connectors

    12. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
  • Page 91: Installing An Optional Supervisory Contact Module Ii

    120 Vac Power Ground Terminal Terminal TB2 Customer Supervisory Contact Interface Terminal TB1 Signal Connections from the UPS Figure 5‐10. Supervisory Contact Module II Terminal Location 5-13 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 92 INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment.
  • Page 93: Figure 5-11. Supervisory Contact Module Ii Tb2

    NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc. NOTE Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of supplying contact current. 5-15 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 94: Accessory Mounting Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐12. Remote Monitor Panel II Dimensions 5-16 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 95: Figure 5-13. Relay Interface Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐13. Relay Interface Module II Dimensions 5-17 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 96: Figure 5-14. Supervisory Contact Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐14. Supervisory Contact Module II Dimensions 5-18 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 97 Section II Operation 5-19 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 98 5-20 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 99: Understanding Ups Operation

    Understanding UPS Operation Figure UPS System Overview The Eaton 9395 UPS is a continuous-duty, solid‐state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic.
  • Page 100: Single Ups

    6.2.1 Modes The Eaton 9395 UPS supports a critical load in five different modes of operation: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive. In Online mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power.
  • Page 101: Energy Saver System Mode

    UPS actively monitors the critical bus for power disturbances. When in this mode, the input and output contactors are closed and the link is maintained through the diode bridge. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 102: Variable Module Management System

    C A U T I O N The critical load is not protected from voltage or frequency fluctuations or power outages while the UPS is in Bypass mode. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 103: Figure 6‐3. Path Of Current Through The Ups In Bypass Mode

    (up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 104: Battery Mode

    164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 105: Single Ups System Oneline Configurations

    Figure 6‐7 on page 6-10 Separate Rectifier Feed, Separate Battery, 9395-275/275 Dual‐Feed Configuration 9395-275/225 Simplified Dual-Fed UPS with Maintenance Figure 6‐8 on page 6-11 9395-275/275 Bypass Panel 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 106: Figure 6‐5. Ups System – Common Rectifier Feed, Common Battery, Dual‐Feed Configuration

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐5. UPS System – Common Rectifier Feed, Common Battery, Dual‐Feed Configuration 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 107: Figure 6‐6. Ups System – Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐6. UPS System – Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 108: Figure 6‐7. Ups System – Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐7. UPS System – Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration 6-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 109: Figure 6‐8. Simplified Dual-Feed Ups With Maintenance Bypass Panel

    (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6‐8. Simplified Dual-Feed UPS with Maintenance Bypass Panel 6-11 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 110: Multiple Ups Distributed Bypass System

    6.4.1 Multiple UPS Parallel System Modes Similar to the single UPS system, the Eaton 9395 UPS parallel system supports a critical load in five different modes of operation. The standard operation modes are: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 111: Online Mode – Distributed Bypass

    Bypass mode. The distributed bypass system automatically returns to Online mode when the overload condition is cleared and system operation is restored within specified limits. 6-13 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 112: Bypass Mode – Distributed Bypass

    If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. 6-14 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 113: Figure 6‐10. Path Of Current Through The Upss In Bypass Mode – Distributed Bypass

    In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to bypass, the remaining UPSs also go to bypass. 6-15 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 114: Battery Mode – Distributed Bypass

    Breakers Closed Output to Main Power Flow Critical Load Open Figure 6‐11. Path of Current through the UPSs in Battery Mode – Distributed Bypass 6-16 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 115: Multiple Ups Distributed Bypass System Oneline Configurations

    Figure 6‐13 on page 6-19 9395-275/275 2+1 and 3+0 Configurations 9395-275/225 Multiple UPS – Distributed Bypass Figure 6‐14 on page 6-20 9395-275/275 3+1 and 4+0 Configurations 6-17 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 116: Figure 6‐12. Typical Distributed Bypass System (1+1 And 2+0 Configurations)

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐12. Typical Distributed Bypass System (1+1 and 2+0 Configurations) 6-18 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 117: Figure 6‐13. Typical Distributed Bypass System (2+1 And 3+0 Configurations)

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐13. Typical Distributed Bypass System (2+1 and 3+0 Configurations) 6-19 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 118: Figure 6‐14. Typical Distributed Bypass System (3+1 And 4+0 Configurations)

    DO NOT install both a source neutral and a bonding jumper. Figure 6‐14. Typical Distributed Bypass System (3+1 and 4+0 Configurations) 6-20 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 119: Ups Operating Instructions

    Control Panel AC Input Breaker CB1 (Optional) (Not available with separate rectifier feed option.) ISBM UPM 1 UPM 2 Figure 7‐1. UPS Controls and Indicators 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 120: Circuit Breakers

    The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 7.3 for use of the operational controls. When the unit powers up, the screen displays the Eaton logo as shown in Figure 7‐2. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
  • Page 121: Status Indicators

    LCD in the UPS status area. This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 122: Using The Lcd And Pushbuttons

    LOAD OFF Figure 7‐3. Parts of the LCD The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, active notices, and load percent and battery runtime for the UPS. If the Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
  • Page 123: Using The Menu

    12 / 11 / 2008 INPUT BATT STSW OUTPUT BYPASS CONTROL LOAD OFF EVENTS METERS SETUP Figure 7‐4. Main Menu and Mimic Screen (Online Mode) 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 124: Display Menu Operation

    The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of Battery – UPM battery time remaining, and battery temperature. Battery temperature must be set up by an authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%, Check Battery is displayed. Statistics The Statistics screen displays the hours on line and the total kW hours used.
  • Page 125 VMMS UPM Redundancy screen. Use the up or down arrow pushbutton to set the number of UPMs. Press SAVE or ABORT. Once the action is completed, the Module Management System Setup screen is displayed. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 126 COM port to be set up, then press the SELECT pushbutton To return to the System Setup screen, press the ESC pushbutton 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 127: Load Off Screen

    7.3.24 on page 7-26 or paragraph 7.4.27 on page 7-46. HOLD LOAD OFF BUTTON FOR 3 SECONDS TO TURN OFF LOAD CANCEL LOAD OFF Figure 7‐5. Load Off Screen 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 128: System Status Screen And Controls

    DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting; Inverter Syncing; Ready; Online UPM 1 Offline; Shutdown, Charger Off; Ready; Ready, Charging; UPM 2 Online, Charger Off; Online, Charging 7-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 129 Charger Off Turns the battery charger off. NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 130: Single Ups Operation

    UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. 7-12 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 131: Enable Energy Saver System Mode From The Ups Command Menu

    The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-13 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 132: Disable Energy Saver System Mode From The Ups Command Menu

    Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 133: Enable Variable Module Management System Mode From The Ups Command Menu

    The UPS transfers to Battery mode and then to Online mode in approximately ten seconds. The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-15 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 134: Start Variable Module Management System High Alert Mode From The Ups Command Menu

    UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 135: Enable Energy Saver System Mode From The Bypass Command Menu

    The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-17 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 136: Disable Energy Saver System Mode From The Bypass Command Menu

    Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 137: Enable Variable Module Management System Mode From The Bypass Command Menu

    System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT 7-19 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 138: Start Variable Module Management System High Alert Mode From The Bypass Command Menu

    Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 139: Starting A Single Upm

    Close the UPS input feeder circuit breaker. Close the UPS Bypass input feeder circuit breaker. If the UPS contains input breaker CB1, close input breaker CB1. 7-21 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 140: Transfer From Online To Bypass Mode

    System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select GO TO BYPASS 7-22 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 141: Transfer From Bypass To Online Mode

    UPM 1 Command menu bar. SELECT The UPM status indicates READY The input, output, and battery contactors open, and the power module remains on. 7-23 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 142: Single Upm Shutdown

    The System Status CONTROLS screen is displayed. On the System Status screen, select the command. The UPS Control Command screen screen is displayed. 7-24 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 143: Ups And Critical Load Shutdown

    Control Command screen is displayed. On the Charger Control Command screen, select CHARGER ON Press the pushbutton on the Charger Command menu bar. SELECT 7-25 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 144: Using The Ups Load Off Pushbutton Or Command

    The System Status CONTROLS screen is displayed. On the System Status screen, select either the or the command. BYPASS 7-26 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 145 7.3.1 on page 7-12 or 7.3.8 on page 7-16. W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 7-27 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 146: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 147: Multiple Ups Distributed Bypass Operation

    UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS outputs remain off until the UPSs transfer to Online mode. 7-29 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 148: Enable Energy Saver System Mode From The Ups Command Menu

    The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-30 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 149: Start Energy Saver System High Alert Mode From The Ups Command Menu

    Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 150: Disable Variable Module Management System Mode From The Ups Command Menu

    The UPS transfers to Battery mode and then to Online mode in approximately ten seconds. The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-32 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 151: Starting The Distributed Bypass System In Bypass Mode

    UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 152: Enable Energy Saver System Mode From The Bypass Command Menu

    The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-34 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 153: Start Energy Saver System High Alert Mode From The Bypass Command Menu

    Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 154: Disable Variable Module Management System Mode From The Bypass Command Menu

    System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT 7-36 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 155: Starting The Ups Upms

    Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 156: Starting A Single Upm

    Close the UPS input feeder circuit breaker. Close the UPS Bypass input feeder circuit breaker. If the UPS contains input breaker CB1, close input breaker CB1. 7-38 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 157: Transfer From Online To Bypass Mode

    Control Command screen is displayed. On the Bypass Control Command screen, select GO TO BYPASS Press the pushbutton on the Bypass Command menu bar. SELECT 7-39 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 158: Transfer From Online To Bypass Mode And Shut Down Upms

    UPM 1 Command menu bar. SELECT The UPM status indicates READY The input, output, and battery contactors open, and the power module remains on. 7-40 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 159: Single Upm Shutdown

    The UPM status indicates SHUTDOWN The power module is turned off. The remaining UPMs continue to supply the critical load. Logic power remains on. 7-41 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 160: Single Upm Restart

    System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select GO TO BYPASS 7-42 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 161: Single Ups Shutdown Using Upm Shutdown

    On the Bypass Control Command screen, select GO TO BYPASS Press the pushbutton on the Bypass Command menu bar. SELECT The UPS being shut down transfer to Bypass mode. 7-43 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 162: Single Ups Restart

    On the UPS being restarted, press the pushbutton on the main menu CONTROLS bar. The System Status screen is displayed. 7-44 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 163: Ups And Critical Load Shutdown

    Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. If the UPSs contain input breakers (CB1), open all UPS input breakers. Open the input and bypass feeder circuit breakers on all UPSs. 7-45 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 164: Charger Control

    When LOAD OFF is selected and held for three seconds, the input, output, battery, and bypass backfeed contactors open, and the power module is turned off on the UPS. 7-46 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 165 7.4.1 on page 7-29 or 7.4.8 on page 7-33. W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 7-47 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 166: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 167: Communication

    Chapter 8 Communication Figure This chapter describes the communication features of the Eaton 9395 UPS and provides information about connecting hardware and using Terminal mode. For terminal wiring information, see paragraph 3.2.3 on page 3-16 and paragraph 4.6 on page 4-17. For location of the customer interface panels and terminals, see Figure 4‐4 on page 4-8 and Figure 4‐13 through Figure 4‐16 starting on page 4-19.
  • Page 168: Enotify Service

    Eaton 9395 UPS: Proactive monitoring, called Anomaly Detection, automatically analyzes the status of the Eaton 9395 UPS on a daily basis. All data gathered from the unit, current and historical, is analyzed at the Customer Reliability Center (CRC) for trending issues.
  • Page 169: Lansafe Power Management Software

    COMMUNICATION The eNotify Service relies on a ConnectUPS-X Web/SNMP Card (or Power Xpert card) installed with the UPS sending one-way status and event e-mails to Eaton Remote Monitoring servers that analyze and store the data. Those servers also take the appropriate actions of sending notifications and reports.
  • Page 170: Terminal Mode

    See paragraph 7.2 on page 7-2, “Using the Control Panel,” for instructions on navigating the control panel. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 171: Event History Log

    If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header. The log in Terminal mode is always in English. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 172: Figure 8‐2. Sample Event History Log

    102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1) 103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1) 104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1) Figure 8‐2. Sample Event History Log 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 173: Building Alarm Monitoring

    RMP II contains backlit status indicators and a local horn. The RMP II can be flush‐mounted or surface‐mounted on a desktop, or secured to a wall. Figure 8‐3 shows an RMP II. Figure 8‐3. Remote Monitor Panel II 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 174 The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 175: Relay Interface Module Ii

    Contacts are closed when approximately two minutes of battery time is remaining before the critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 176: Supervisory Contact Module Ii

    BYPASS NOT AVAILABLE TB2‐10 through TB2‐12 ON BATTERY TB2‐13 through TB2‐15 UPS ALARM TB2‐16 through TB2‐18 ON BYPASS TB2‐19 through TB2‐21 SHUTDOWN IMMINENT TB2‐22 through TB2‐24 8-10 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 177: Ups Maintenance

    The likelihood of such shock is reduced if such grounds are removed during installation and maintenance. When replacing batteries, use the same number of sealed, lead‐acid batteries. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 178: Performing Preventive Maintenance

    Check the UPS air filters (located behind the front panels) and wash or replace as necessary. See Figure 9‐1 for filter locations. The ISBM filter size is 12” 20” 0.25” and the UPM filter sizes are 20” 44” 0.25”. Contact an Eaton service representative for replacement filters. To remove the filters: a.
  • Page 179: Periodic Maintenance

    Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 180: Battery Maintenance

    Maintenance Training A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Help Desk (see page 1-9).
  • Page 181: Product Specifications

    Configurable per UPM at nominal line voltage: Up to 120A with less than 85% load Up to 80A with 100% load Battery Shunt Trip 48 Vdc 10-1 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 182: Ups Output

    Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse Immunity without damage and with no disturbance or adverse effect to the critical load. 10-2 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 183 Eaton-built battery cabinets (individually and collectively, the ”Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton.
  • Page 184 WARRANTY This page intentionally left blank. 164201710 Rev 2 www.eaton.com\powerquality Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual...
  • Page 186 *1642017102* 164201710 2...