INSTALLING OPTIONS AND ACCESSORIES
5-14
Eaton Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service
Engineer. Contact an Eaton service representative to schedule a date.
9.
Install wiring between the SCM II terminal block TB2 and the monitoring
equipment. See Figure 5‐10 for terminal block location and Figure 5‐11 for
terminal assignments.
10. Close the front door and secure the latch.
11. Restart the UPS. See Chapter 7, "UPS Operating Instructions," for startup
instructions.
Bypass Not Available
Shutdown Imminent
Figure 5‐11. Supervisory Contact Module II TB2
NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
NOTE Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of supplying
contact current.
System Normal
No Redundancy
On Generator
On Battery
UPS Alarm
On Bypass
S
P-164000710 Rev 1
www.eaton.com/powerquality