Eaton Power Xpert 9395 High Performance Installation And Operation Manual
Eaton Power Xpert 9395 High Performance Installation And Operation Manual

Eaton Power Xpert 9395 High Performance Installation And Operation Manual

Table of Contents

Advertisement

Quick Links

®
®
Eaton
Power Xpert
9395 High Performance (9395P-900) UPS
900 kW, 900 kVA
Installation and Operation Manual
For use with Two UPM (450–600 kVA),Three UPM (675–900 kVA), and Plus 1 (675–900 kVA) UPS
Models
p/n: 164000501
Revision 12

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Power Xpert 9395 High Performance and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton Power Xpert 9395 High Performance

  • Page 1 ® ® Eaton Power Xpert 9395 High Performance (9395P-900) UPS 900 kW, 900 kVA Installation and Operation Manual For use with Two UPM (450–600 kVA),Three UPM (675–900 kVA), and Plus 1 (675–900 kVA) UPS Models p/n: 164000501 Revision 12...
  • Page 2 Eaton reserves the right to change specifications without prior notice. Eaton and Power Xpert are registered trademarks and PredictPulse is a trademark of Eaton or its subsidiaries and affiliates. CA Technologies is a registered trademark of CA, Inc. IBM and AS/400 are registered trademarks of International Business Machines Corporation.
  • Page 3 Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, and trusting us to maintain your business continuity and preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host of threats including power outages, surges, lighting strikes, and enable you to monitor and control your power infrastructure.
  • Page 4 Licensee or other subsidiary of Licensee’s parent, to copy, distribute, or otherwise transfer the Firmware without the prior written consent of Eaton. Licensee may transfer the Firmware directly to a third party only in connection with the sale of the Eaton product in which it is installed.
  • Page 5 TO THE EXTENT PERMITTED BY APPLICABLE LAW, THE USE OF THE PRODUCT IS AT LICENSEE’S SOLE RISK. 5.0 GENERAL PROVISIONS 5.1 Update Policy. Eaton may from time to time, but has no obligation to, create Updates of the Firmware or components thereof. 5.2 Limitation on Liability. NOTWITHSTANDING ANY PROVISION OF THIS AGREEMENT TO THE...
  • Page 6 Firmware pursuant to license arrangements between Eaton and such third parties. Third Party Licensor components in the Firmware are not licensed or warranted under the terms of this document, but are instead subject to the Third Party Licensors’...
  • Page 7 Eaton, the disclosure of which would cause substantial harm to Eaton that could not be remedied by the payment of damages alone and such confidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton.
  • Page 9 3.2.1 General Storage Requirements for UPS Equipment..................17 3.2.2 Environmental and Installation Considerations ..................18 3.2.3 Installation Considerations ........................18 3.2.4 UPS System Power Wiring Preparation ....................35 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 10 6.2.4 Variable Module Management System ....................126 6.2.5 Bypass Mode........................... 126 6.2.6 Battery Mode........................... 128 6.3 Single UPS System Oneline Configurations ....................130 6.4 Multiple UPS Distributed Bypass System..................... 145 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 11 7.4.6 Disable Variable Module Management System Mode................186 7.4.7 Start Variable Module Management System High Alert Mode ..............186 7.4.8 Starting the UPS in Bypass Mode ......................187 7.4.9 Starting the UPMs ..........................188 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 12 8.2.2 Installing PredictPulse........................210 8.3 Power Management Software........................211 8.4 Building Alarm Monitoring ........................211 8.5 General Purpose Relay Contact ......................... 211 8.6 Remote Monitor Panel II .......................... 212 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 13 1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s ................................................... . 2 2 2 2 3 3 10.1 Model Numbers ........................... 223 10.2 Specifications............................223 10.2.1 UPS Input............................223 10.2.2 UPS Output ........................... 224 10.2.3 UPS Environmental ......................... 225 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12 xiii...
  • Page 14 Table of Contents Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 15 Power Xpert 9395P-900 Two UPM UPS with 1 FI-UPM ................3 Figure 3. Power Xpert 9395P-900 Three UPM UPS .................... 4 Figure 4. Eaton Xpert 9395P-900 Three UPM Plus 1 FI-UPM ................5 Figure 5. UPS Cabinet Dimensions – Three UPM (Front View) ................23 Figure 6.
  • Page 16: Table Of Contents

    Three UPM, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static Switch ............................. 135 Figure 76. Two UPM, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch ............................. 136 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 17 Figure 112. Battery Meters Screen ........................ 171 Figure 113. System Events Screen ........................ 172 Figure 114. User Log Screen ........................173 Figure 115. User Log Detail Screen........................ 173 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12 xvii...
  • Page 18 ISBM Section Air Filter Locations – Continuous Static Switch .............. 219 Figure 140. FI-UPM Air Filter Location ......................220 Figure 141. FI-UPM Air Filter Location ......................221 xviii Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 19 UPS External Power Cable Terminations for Three/Four UPM Models ............48 Table 21. Supplied External Wiring Terminal Hardware Kit ................... 49 Table 22. Recommended Installation Parts and Tools (Not Supplied by Eaton) ............49 Table 23. 480V Power Cable Conduit Requirements ..................50 Table 24.
  • Page 20 Table 42. RMP II Status Indicators........................ 213 Table 43. Customer Interface Connectors...................... 214 Table 44. SCM II Status Indicators and Connections..................215 Table 45. UPS Filter Sizes........................... 218 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 21 C C h h a a p p t t e e r r 1 1 I I n n t t r r o o d d u u c c t t i i o o n n The Eaton ®...
  • Page 22 UPM section containing two UPMs each UPM rated for a maximum of 300 kVA for a total maximum of 600 kVA. Figure 1. Power Xpert 9395P-900 Two UPM UPS UPM SECTION ISBM or IOM SECTION Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 23 900 kVA for 480V models and 825 kVA for 415V/400V/380V models. Figure 2. Power Xpert 9395P-900 Two UPM UPS with 1 FI-UPM FI-UPM UPM SECTION ISBM or IOM SECTION Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 24 UPM section containing three UPMs. Each UPM is rated for a maximum of 300 kVA for a total maximum of 900 kVA. Figure 3. Power Xpert 9395P-900 Three UPM UPS UPM SECTION ISBM or IOM SECTION Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 25 Service Engineer, or the warranty terms become void (see Section ). This service is offered as part of the sales contract for the UPS system. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 26 UPS cabinet to allow for future expansion using an external module. Consult the Eaton® Power Xpert® 9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR) Installation Manual (P-164000580) for specifics on battery cabinet usage with the Power Xpert 9395P-600.
  • Page 27 ISBM section and is wired directly to the UPS. No input or output wiring changes are needed for a capacity increase if the original installation was wired for increased capacity. Operation remains the same as the original UPS. Refer to the Eaton ® Power Xpert ®...
  • Page 28 1 1 . . 3 3 . . 8 8 I I n n h h e e r r e e n n t t R R e e d d u u n n d d a a n n c c y y To deliver greater reliability, the Power Xpert 9395P-600 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy.
  • Page 29 PredictPulse™ Remote Monitoring and Management Service – PredictPulse is a subscription monitoring and management service from Eaton that collects and analyzes data from connected power infrastructure devices, providing us with the insight needed to make recommendations and take action on your behalf.
  • Page 30 (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 31 F F o o r r M M o o r r e e I I n n f f o o r r m m a a t t i i o o n n Refer to the Eaton 9395/9395P Integrated Battery Cabinet (Model I085 and 1085HR) Installation Manual (P- 164000580) for the following additional information: •...
  • Page 32 Introduction Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 33 Do not check UPS operation by any action that includes removal of the earth (ground) connection with loads attached. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton ® Power Xpert ®...
  • Page 34 The operating environment should be maintained within the parameters stated in this manual. • Keep surroundings uncluttered, clean, and free from excess moisture. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 35 End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. Eaton ® Power Xpert ®...
  • Page 36 Les passages de fourche à l’extrémité de l’armoire peuvent servir lors des petits déplacements, et ce, si les fourches sont en position horizontale sans pointer vers le haut. Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. Eaton ® Power Xpert ®...
  • Page 37 Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms specified on the Eaton website in section will become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 38 If the installation location does not meet the recommended environment, contact Eaton service representative for further information. 3 3 . . 2 2 . . 3 3 I I n n s s t t a a l l l l a a t t i i o o n n C C o o n n s s i i d d e e r r a a t t i i o o n n s s The UPS system installation must meet the following guidelines: •...
  • Page 39 21. Dimensions are in millimeters (inches). Table 2 does not include the weight of the Field Installed UPM (FI-UPM). For FI-UPM weights and dimensions, refer to the Eaton 9395P Field Installed UPM Mechanical Installation Manual (P-164000503), listed in paragraph 1.8 For More Information.
  • Page 40 UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton’s Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
  • Page 41 Table 4. 480V Air Conditioning and Ventilation Requirements During Full Load Operation Heat Rejection Rating Input/Output BTU/hr x1000 Ventilation Required for Model Voltage (kg-cal/hr) Cooling Air Exhaust Eaton 9395P-900/900* 900 kVA 480/480 118 (29.7) (CSS) 900 kVA Eaton 9395P-900/900 900 kVA 480/480 108.3 (27.3)
  • Page 42 Table 6. 400V Air Conditioning and Ventilation Requirements During Full Load Operation Heat Rejection Rating Input/Output BTU/hr x1000 Ventilation Required for Model Voltage (kg-cal/hr) Cooling Air Exhaust Eaton 9395P-900/825 825 kVA 400/400 116.1 (29.3) (CSS) 825 kVA Approximately 3300 liter/sec (7000 CFM) Eaton 9395P-900/750 900 kVA 400/400 105.6 (26.6)
  • Page 43 UPS Installation Plan and Unpacking Figure 5. UPS Cabinet Dimensions – Three UPM (Front View) Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 44 UPS Installation Plan and Unpacking Figure 6. UPS Cabinet Dimensions – Two UPM (Front View) 1880 [74.0] 3036.9 [119.5] Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 45 UPS Installation Plan and Unpacking Figure 7. UPS Cabinet Dimensions (Right Side View) [32.7] [1.6] Dimensions are in millimeters [inches]. [35] Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 46 For 4-wire systems only 1705 [67.1] Dimensions are in millimeters [inches]. Figure 9. ISBM Section Dimensions (Top View) 263.53 [10.4] 644.53 [25.4] Front Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 47 Figure 10. ISBM Section Dimensions (Bottom View) Front Dimensions are in millimeters [inches]. Figure 11. UPM Section Dimensions – Three UPM (Front View) 1880 [74.0] 1871.9 [73.7] Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 48 Figure 12. UPM Section Dimensions – Three UPM (Top View) Front Dimensions are in millimeters [inches]. Figure 13. UPM Section Dimensions – Two UPM (Front View) 1880 [74.0] 1331.9 [52.4] Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 49 UPS Installation Plan and Unpacking Figure 14. UPM Section Dimensions – Two UPM (Top View) 34.44 1015.43 37.14 [1.4] [40.0] [1.5] 758.83 [29.9] Front Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 50 1880 [74.0] 735.9 [29.0] Dimensions are in millimeters [inches]. Figure 16. UPM Section Dimensions – FI-UPM (Top View) 510.1 [20.1] 758.83 [29.9] Front Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 51 THREE UPMS 1880 [74.0] 361 [14.3] 900+1 kVA UPS 900 [35.4] 362 [14.3] 918 [36.1] FI-UPM 850 [33.5] 357 [14.1] ISBM/IOM 362 [14.3] 918 [36.1] 3XUPM Side View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 52 THREE UPMS 1880 [74.0] 361 [14.3] 900-1 kVA UPS 900 [35.4] 362 [14.3] 918 [36.1] FI-UPM 850 [33.5] 357 [14.1] ISBM/IOM 362 [14.3] 918 [36.1] 2XUPM Side View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 53 DIMENSIONS MM [IN] CENTER OF GRAVITY - THREE UPMS 1880 [74.0] 360 [14.3] 896 [35.3] 900 kVA UPS 850 [33.5] ISBM 357 [14.1] 362 [14.3] 918 [36.1] 3XUPM Side View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 54 DIMENSIONS MM [IN] CENTER OF GRAVITY - TWO UPMS 1880 [74.0] 360 [14.3] 896 [35.3] 900-1 kVA UPS 850 [33.5] ISBM 357 [14.1] 362 [14.3] 918 [36.1] 2XUPM Side View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 55 • The Eaton 9395P 480V unit is designed for operation on a grounded-wye source of supply. There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads.
  • Page 56 17. Wire sizes listed are for copper wiring only. Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 825 kVA in these tables. Eaton ® Power Xpert ®...
  • Page 57 Figure 82 NOTE: Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 58 (50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the return current path and cause a loss of all phase-to-neutral loads. If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the transition. Eaton ® Power Xpert ®...
  • Page 59 Figure 82 NOTE: Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 60 (50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the return current path and cause a loss of all phase-to-neutral loads. If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the transition. Eaton ® Power Xpert ®...
  • Page 61 Figure 82 NOTE: Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 62 (50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the return current path and cause a loss of all phase-to-neutral loads. If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the transition. Eaton ® Power Xpert ®...
  • Page 63 Figure 82 NOTE: Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 64 (50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the return current path and cause a loss of all phase-to-neutral loads. If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the transition. Eaton ® Power Xpert ®...
  • Page 65 72. Callout letters A, C, and D map to Figure NOTE: Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 66 Table 19 supplied terminal hardware, and Table 22 for recommended installation parts and tools not supplied by Eaton. The torque values listed in Table 18 for the M8 studs are the maximum allowable. Tightening further will risk breaking or twisting the stud.
  • Page 67 3E4A (UPM 4) DC Input to UPM Section 1E5A (UPM 1) 6 – stud mounting 2E5A (UPM 2) Negative 14.2 (10.4) (2 per UPM) 3E5A (UPM 3) 3E5A (UPM 4) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 68 Table 20 for power cable terminations, Table 21 supplied terminal hardware, and Table 22 for recommended installation parts and tools not supplied by Eaton. Figure 40 through Figure 43 show the location of the power cable terminals inside the UPS.
  • Page 69 Washer Output, and Ground 180200001-07 Rectifier Input, Bypass Input, Battery Input, Output, and Ground NOTE Bypass terminations are not applicable to IOM configurations. Table 22. Recommended Installation Parts and Tools (Not Supplied by Eaton) Quantity Part Size Manufacturer Part Number...
  • Page 70 Conduit Conduits Conduit Trade Size AC Input to UPS Rectifier (A, B, C, Ground) 480 Vac AC Input to Bypass and Output Eaton 9395P-900/900* (A, B, C, Ground) Eaton 9395P-900/900 Eaton 9395P-900/825 Battery (Common (Positive, Negative, Ground) Battery) AC Input to UPS Rectifier...
  • Page 71 (Common (Positive, Negative, Ground) Battery) AC Input to UPS Rectifier (A, B, C, Ground) 415 Vac AC Input to Bypass and Output Eaton 9395P-900/675 (A, B, C, Ground) Battery (Common (Positive, Negative, Ground) Battery) AC Input to UPS Rectifier (A, B, C, Ground)
  • Page 72 Trade Size Conduits AC Input to UPS Rectifier (A, B, C, Ground) 400 Vac 380 Vac AC Input to Bypass and Output Eaton 9395P-900/825 (A, B, C, Ground) Battery (Common (Positive, Negative, Ground) Battery) AC Input to UPS Rectifier (A, B, C, Ground)
  • Page 73 (Common (Positive, Negative, Ground) Battery) AC Input to UPS Rectifier (A, B, C, Ground) 400 Vac 380 Vac AC Input to Bypass and Output Eaton 9395P-900/450 (A, B, C, Ground) See Note 1 Battery (Common (Positive, Negative, Ground) Battery) Battery...
  • Page 74 1000A 1000A NOTE Because of the future upgradability to a fully rated 900 kW UPS with the addition of the FI-UPM, Eaton recommends using the breaker size specified for a 1100 kW UPS. To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings...
  • Page 75 800A 800A NOTE Because of the future upgradability to a fully rated 900 kW UPS with the addition of the FI-UPM, Eaton recommends using the breaker size specified for a 1100 kW UPS. There is no manual DC disconnect device within the UPS.
  • Page 76 UPS Installation Plan and Unpacking Table 28. Recommended DC Input Battery Disconnect Ratings – Common Battery Input Rating UPS Model 480V Eaton 9395P-900/900* Eaton 9395P-900/900 2500A Eaton 9395P-900/825 Eaton 9395P-900/750 2000A Eaton 9395P-900/675 Eaton 9395P-900/600* Eaton 9395P-900/600 Eaton 9395P-900/550 2500A...
  • Page 77 NOTE 2 HIGH ALERT mode is desired because any loads with a leading power factor will not be seen by the generator. Rectifier operation will be much softer while on generator thereby increasing overall system stability Eaton ® Power Xpert ®...
  • Page 78 Les sections de l’onduleur sont lourdes (voir le Table 2). Suivre attentivement les instructions de déchargement et de déballage pour eviter de renverser les armoires, ce qui pourrait causer de graves blessures. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 79 Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. Carefully inspect the outer packaging for evidence of damage during transit. Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately.
  • Page 80 Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
  • Page 81 UPS Installation Plan and Unpacking Figure 22. UPS Cabinet as Shipped on Pallet (ISBM Section) For 4-wiring systems only Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 82 UPS Installation Plan and Unpacking Figure 23. UPS Cabinet as Shipped on Pallet (UPM Section) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 83 Les sections de l’onduleur sont lourdes (voir le tableau Table 2). Suivre attentivement les instructions de déchargement et de déballage pour éviter de renverser les armoires, ce qui pourrait causer de graves blessures. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 84 If not already accomplished, use a forklift or pallet jack to move the UPS to the installation area, or as close as possible, before unloading from the pallet. Use a forklift or pallet jack to install the UPS. Insert the Eaton ®...
  • Page 85 27). Remove the right side shipping bracket. Figure 24. Removing the ISBM Section Left Side Shipping Bracket Front Door Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 86 Carefully lower the UPS cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4.3 Mechanically Joining the Sections. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 87 UPS System Installation Figure 26. Removing the UPM Section Left Side Shipping Bracket UPM Removable Front Panels Pallet Shipping Bracket Bolts Wireway Panel Shipping Bracket Left Side Shipping Bolts Bracket Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 88 Lift the panel straight up to remove it from the panel hanger brackets at the top of the cabinet. Remove the screws securing the top and bottom internal safety shield panels and remove the panels. Retain the hardware for later use. Eaton ® Power Xpert ®...
  • Page 89 28). Retain the hardware for later use. Use care during installation to protect components mounted on the right side of the ISBM section and the intercabinet wiring harnesses attached to the left side UPM section from damage. Eaton ® Power Xpert ®...
  • Page 90 11. Locate the hardware kit (packed inside a drawstring bag tied to the left middle panel of the UPM section). Locate two flat brackets and screws from the hardware kit. Align the holes in the flat brackets over holes in Eaton ®...
  • Page 91 UPM wireway on the left side of the UPM section (see Figure Locate the AC and DC input intercabinet power wiring harnesses (long cables labeled xG1, xG2, and xG3). Remove wire ties as necessary and uncoil the cables. Eaton ® Power Xpert ®...
  • Page 92 Figure 32). This hardware is used by an Eaton Customer Service Engineer to install a Field Installed UPM (FI-UPM). 13. Locate the ground braid in the bottom left front corner of the UPM section. The ground braid is secured at the factory to the UPM section ground bolt.
  • Page 93 27. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7 Distributed Bypass Tie Cabinet Installation; otherwise, proceed to paragraph 4.8 Installing UPS External and Battery Power Wiring Eaton ® Power Xpert ®...
  • Page 94 UPS System Installation Figure 31. ISBM Section Intercabinet Power Terminal Locations AC Input to Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 95 NOTE On a UPS without CB1, UPM input wiring terminations are in the same positions on the bus bars installed in the place of CB1. NOTE On a UPS configured as an IOM, UPM input wiring terminations are the same as an ISBM configuration. Eaton ®...
  • Page 96 Cable 3G3 Red – UPM 3 (3E4A) UPM 3 (3E5A) Cable 3G3 Black Cable 3G3 Red (Not used with Two UPM systems.) (Not used with Two UPM systems.) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 97 UPM 1 Cable 1G4 & 1G5 Gray UPM 2 Cable 2G4 & 2G5 Gray Neutral from UPMs (E12A) UPM 3 Cable 3G4 & 3G5 Gray UPM 4 Cable 4G4 & 4G5 Gray Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 98 Harness Front Front UPM Wireway Location of P50, P51, and P70 Harnesses Location of RJ-45 Coiled CAN Cable ISBM Section Right Side View UPM Section Left Side View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 99 UPS System Installation Figure 36. Pl1 Interface Board Location Pl1 Interface Board Front ISBM Section Right Side Inside View Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 100 F F i i e e l l d d I I n n s s t t a a l l l l e e d d U U P P M M I I n n s s t t a a l l l l a a t t i i o o n n If installing a Plus 1 configuration with an FI-UPM, install the FI-UPM using the instructions in the Eaton®...
  • Page 101 Identify all conduit requirements and mark their location. Drill and punch all conduit holes in the bottom conduit plate prior to mounting on the ISBM section. Install the conduit plate and install all conduit runs into the plate. Pull wiring through conduit into the ISBM section wiring area. Eaton ® Power Xpert ®...
  • Page 102 ISBM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) Three UPM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) Two UPM Section Front Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 103 ISBM section. See paragraph 3.2.4 UPS System Power Wiring Preparation for wiring and termination requirements. If wiring a distributed bypass system, proceed to Step 9; otherwise, proceed to Step 11. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 104: Figure 40. Isbm Section Power Terminal Locations

    See paragraph 3.2.4 UPS System Power Wiring Preparation for wiring and termination requirements. 12. Proceed to paragraph 4.8.2 Battery Power Wiring. Figure 40. ISBM Section Power Terminal Locations NOTE Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 105: Figure 41. Isbm Section Power Terminal Detail Aa

    4 4 . . 8 8 . . 2 2 B B a a t t t t e e r r y y P P o o w w e e r r W W i i r r i i n n g g When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10 Product Specifications for maximum battery charger currents. Eaton ® Power Xpert ®...
  • Page 106 Chapter 10 Product Specifications sur les notices techniques pour connaître les tensions maximales du chargeur de batteries.Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement. To install wiring to connections: NOTE An installed FI-UPM is always designated as UPM 4.
  • Page 107: Figure 42. Ups Power Terminal Detail Bb - Common Battery

    UPS System Installation Figure 42. UPS Power Terminal Detail BB – Common Battery DC Input from Battery + (E4) Front DC Input from Battery – (E5) Section B–B Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 108: Figure 43. Ups Power Terminal Detail Bb - Separate Battery

    Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. AVERTISSEMENT! Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur n’est pas totalement débranché. Eaton ® Power Xpert ®...
  • Page 109 10. Reinstall the top internal safety shield panel and secure with the retained hardware. 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. Eaton ® Power Xpert ®...
  • Page 110: Figure 44. Isbm Section Interface Terminal Locations

    UPS System Installation Figure 44. ISBM Section Interface Terminal Locations Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 111 Default function set for charger off. Building Alarm 3 Return Input: Programmable UPS alarm, activated by a remote dry contact closure. Building Alarm 4 Default function set for on generator. Default: On Generator Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 112: Figure 45. Interface Terminal Detail

    NOTE “Return” indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. Figure 45. Interface Terminal Detail X-Slot Communication Bays See Figure”Terminal Blocks TB1, TB2, and TB3 Connector Assignments” for terminal assignments. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 113: Figure 46. Typical Alarm Relay Connection

    NOTE Alarm relay normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG. Eaton ® Power Xpert ®...
  • Page 114: Figure 47. Terminal Blocks Tb1, Tb2, And Tb3 Connector Assignments

    All control wiring and relay and switch contacts are customer-supplied. NOTE The building alarms can be programmed to display the alarm functional name. NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Eaton ® Power Xpert ®...
  • Page 115 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. If wiring X-Slot connections, proceed to paragraph 4.9.3 X-Slot Connections; otherwise, proceed to Step 13. Close the door and secure the latch. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 116: Figure 48. Typical Battery Interface Connection - Common Battery System

    When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see paragraph 1.9 Getting Help). To install wiring to connections: Eaton ®...
  • Page 117: Figure 50. X-Slot Communication Bays

    A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location away from where the UPS is installed. Figure 51 shows a REPO switch. Eaton ® Power Xpert ®...
  • Page 118: Figure 51. Repo Switch

    The REPO switch must be a normally-open or normally-closed latching–type switch not tied into any other circuits. NOTE 5 This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide. NOTE 6 The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
  • Page 119: Figure 52. Normally-Open Repo Switch Wiring

    13. Reinstall the top internal safety shield panel and secure with the retained hardware. 14. Reinstall the front door removed in Step 4 and secure with the retained hardware. 15. Close the door and secure the latch. Eaton ® Power Xpert ®...
  • Page 120: Figure 53. Normally Closed Repo Switch Wiring

    NOTE REPO switch rating is 24 Vdc, 1A minimum. NOTE The REPO switch must be a latching-type switch not tied to any other circuits. NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Eaton ® Power Xpert ®...
  • Page 121 (see Section paragraph ). This service is offered as part of the sales contract for the UPS system. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 122 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) o The debris shield covering the UPS cabinet ventilation grill is removed. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton ®...
  • Page 123 Pull-chain wiring between the UPS cabinets is properly installed. o Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton ®...
  • Page 124 UPS System Installation Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 125 In addition, this card can be used to connect optional system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface Module II, or a Supervisory Contact Module II to the UPS. Eaton ® Power Xpert ®...
  • Page 126: Figure 55. Hot Sync Can Bridge Card

    Install the Hot Sync CAN Bridge Card into an open X-Slot communication bay on the front of the UPS. See Figure 44 Figure 50 for X-Slot communication bay locations. To locate the appropriate terminals on the Hot Sync CAN Bridge Card, see Figure 56 Table Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 127: Figure 56. Hot Sync Can Bridge Card Connections

    Alarm Relay NO Normally open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L CAN Input for parallel operation. Can H Shield Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 128 NOTE Setup of the Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
  • Page 129: Figure 57. Distributed Bypass System Ups Can Wiring Without Mobs

    To UPS 3 CAN Bridge Card To UPS 4 CAN Bridge Card Card Card (If Installed) (If Installed) J3 8 (L) J3 8 (L) J3 8 (L) J3 8 (L) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 130: Figure 58. Distributed Bypass Pull-Chain Wiring Without Mobs

    TB2–1 TB2–1 TB2–1 TB2–1 (Pull Chain) (Pull Chain) (Pull Chain) (Pull Chain) TB2–2 TB2–2 TB2–2 TB2–2 (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 131: Figure 59. Distributed Bypass Pull-Chain Wiring With Mobs

    NOTE External CAN connections between UPS cabinets require shielded twisted-pair wire. NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. NOTE Always m contact operation prior to wiring. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 132: Table 35. Pull-Chain Wiring Terminations With Mobs

    Securely mount the RMP II at the desired location. See Figure 65 for mounting hole locations. NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the device and the UPS cabinet. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 133: Figure 60. Remote Monitor Panel Ii And Remote Monitor Panel Ii Terminal Locations

    Figure 60. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations Ground Terminal Terminal TB1 Signal Connections from the UPS Terminal TB3 120 Vac Power Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 134: Figure 61. Remote Monitor Panel Ii, Relay Interface Module Ii, Or Supervisory Contact Module Ii Wiring

    If a fuse replacement does not correct the problem, contact an Eaton service representative for verification that the RMP II is working correctly. 12. To test the indicator lamps, press and hold the horn silence pushbutton for three seconds. All lamps should illuminate, and the horn sounds continuously until you release the pushbutton.
  • Page 135 Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior to making connections with J1 through J4 (see...
  • Page 136: Figure 62. J1, J2, J3, And J4 15-Pin D-Sub Connectors

    Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see Figure 39). Reinstall the conduit landing plate. Install conduit between the UPS and SCM II. See Figure 67 for SCM II knockout hole location. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 137: Figure 63. Supervisory Contact Module Ii Terminal Location

    Connections from the UPS NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment. See...
  • Page 138: Figure 64. Supervisory Contact Module Ii Tb2

    A A c c c c e e s s s s o o r r y y M M o o u u n n t t i i n n g g D D i i m m e e n n s s i i o o n n s s Figure 65 through Figure 67 show the dimensions of the RMP II, the RIM II, and the SCM II. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 139: Figure 65. Remote Monitor Panel Ii Dimensions

    Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 140: Figure 66. Relay Interface Module Ii Dimensions

    Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 141: Figure 67. Supervisory Contact Module Ii Dimensions

    Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 142 Installing Options and Accessories Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 143: Figure 68. Main Elements Of The Ups System

    U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 9395P-900 UPS is a continuous-duty, solid–state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 144 6 6 . . 2 2 . . 1 1 M M o o d d e e s s The Eaton 9395P-900 UPS supports a critical load in five different modes of operation: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 145: Figure 69. Path Of Current Through The Ups In Online Mode

    If commercial power voltage or frequency disturbances are detected, the system forward transfers to Battery mode for minor disturbances and then to double-conversion mode for more severe disturbances. During a Eaton ® Power Xpert ®...
  • Page 146 Bypass mode of operation. The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) static switch (SSW) and a backfeed protection contactor K5. The static switch is rated as a continuous-duty device that is used anytime Eaton ® Power Xpert ®...
  • Page 147: Figure 70. Path Of Current Through The Ups In Bypass Mode

    If the UPS transfers to Bypass mode from Online mode due to any reason other than operator intervention, the UPS automatically attempts to transfer back to Online mode (up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. Eaton ® Power Xpert ®...
  • Page 148: Figure 71. Path Of Current Through The Ups In Battery Mode

    NOTE On a UPS configured as an IOM, the bypass input, static switch, bypass breaker (CB4), and K5 are not present. NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Eaton ®...
  • Page 149 Understanding UPS Operation Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 150: Table 38. Oneline Configurations

    The following voltages apply: 380V, 400V, 415V, 480V and 600V. Table 38. Oneline Configurations Oneline Drawing UPS Model System Type Eaton 9395P-900/900* Eaton 9395P-900/900 Single Reverse Transfer UPS – Four UPM, Common Rectifier Feed, Figure 72 Eaton 9395P-900/825...
  • Page 151 Understanding UPS Operation Table 38. Oneline Configurations (Continued) Oneline Drawing UPS Model System Type Eaton 9395P-900/900* Eaton 9395P-900/900 Single Reverse Transfer UPS – Three UPM, Common Rectifier Feed, Figure 80 Eaton 9395P-900/825 Common Battery, IOM Configuration Eaton 9395P-900/750 Eaton 9395P-900/675...
  • Page 152: Figure 72. Four Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 153: Figure 73. Four Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 154: Figure 74. Three Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 155: Figure 75. Three Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 156: Figure 76. Two Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 157: Figure 77. Two Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 158: Figure 78. Three Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 159: Figure 79. Three Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 160: Figure 80. Three Upm, Common Rectifier Feed, Common Battery, Iom Configuration

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 161: Figure 81. Three Upm, Common Rectifier Feed, Separate Battery, Iom Configuration

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 162: Figure 82. Four Upm, Common Rectifier Feed, Common Battery, Iom Configuration

    BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 163: Figure 83. Four Upm, Common Rectifier Feed, Separate Battery, Iom Configuration

    (Not supplied with the UPS) (Not supplied with the UPS) Service Connector NOTE Callout letters , and map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 164: Figure 84. Simplified Dual-Feed Ups With Maintenance Bypass Panel

    DO NOT use a single feed or a single feeder breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass input breaker (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Eaton ® Power Xpert ®...
  • Page 165 6 6 . . 4 4 . . 1 1 M M u u l l t t i i p p l l e e U U P P S S P P a a r r a a l l l l e e l l S S y y s s t t e e m m M M o o d d e e s s Similar to the single UPS system, the Eaton 9395P-900 UPS parallel system supports a critical load in five different modes of operation.
  • Page 166: Figure 85. Path Of Current Through The Upss In Online Mode - Distributed Bypass

    UPS 2 Output UPS 2 Battery UPS 3 Output UPS 3 Battery UPS 4 Output UPS 4 Battery Breakers Closed Output to Main Power Flow Critical Load Open Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 167: Figure 86. Path Of Current Through The Upss In Bypass Mode - Distributed Bypass

    UPS 2 Output UPS 2 Battery UPS 3 Output UPS 3 Battery UPS 4 Output UPS 4 Battery Breakers Closed Output to Main Power Flow Critical Load Open Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 168 UPMs begin shutting down until there are no longer enough UPMs online to support the connected load. When this event occurs, the system shuts down. If the bypass source is available, the system transfers to bypass instead of shutting down. Eaton ® Power Xpert ®...
  • Page 169: Figure 87. Path Of Current Through The Upss In Battery Mode - Distributed Bypass

    Depending on the total load and the duration of the battery discharge, battery and rectifier input current limit alarms may be seen for a short time due to the current required to recharge the batteries. Eaton ® Power Xpert ®...
  • Page 170 UPM in the UPSs, but represent each UPS in the distributed bypass system. The following voltages apply: 380V, 400V, 415V, 480V and 600V. Oneline Drawing System Type UPS Model Eaton 9395P-900/900* Eaton 9395P-900/900 Eaton 9395P-900/825 Eaton 9395P-900/750 Eaton 9395P-900/675 Figure 88 Multiple UPS –...
  • Page 171: Figure 88. Typical Distributed Bypass System (1+1 And 2+0 Configurations)

    NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal Critical Load structure of each UPS is shown in the Single UPS System Oneline Configurations Section 6.3. Eaton ® Power Xpert ®...
  • Page 172: Figure 89. Typical Distributed Bypass System (2+1 And 3+0 Configurations)

    NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal Critical Load structure of each UPS is shown in the Single UPS System Oneline Configurations Section 6.3. Eaton ® Power Xpert ®...
  • Page 173: Figure 90. Typical Distributed Bypass System (3+1 And 4+0 Configurations)

    NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal Critical Load structure of each UPS is shown in the Single UPS System Oneline Configurations Section 6.3. Eaton ® Power Xpert ®...
  • Page 174 Understanding UPS Operation Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 175: Figure 91. Ups Controls And Indicators

    Identifies the touchscreen control panel and the location of the CB1 circuit breaker (optional). Figure 91. UPS Controls and Indicators Touchscreen Control Panel Input Breaker CB1 (optional) ISBM ISBM (Right Door Removed) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 176: Figure 92. Ups Color Touchscreen Control Panel Location (Typical)

    For a description of the UPS control panel functions, see paragraph 7.3 Using the Color Touchscreen Control Panel. Figure 92. UPS Color Touchscreen Control Panel Location (Typical) Color Touchscreen Control Panel ISBM Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 177: Figure 93. Ups Color Touchscreen Control Panel (Typical)

    When the unit powers up, the screen displays as shown in Figure 93. When power is applied to the system, the display advances to the Sign In screen shown in Figure Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 178: Table 39. Status Indicators

    Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right corner of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password request pop-up (see Figure 95). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 179: Figure 94. Parts Of The Touch Screen

    The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
  • Page 180: Figure 95. Sign In Or Password Request Screen

    Level Name Passcode USER NONE USER CONTROL 1111 USER + CONTROL CONFIGURATION 0101 USER + CONTROL + CONFIGURATION Service Only USER + CONTROL + CONFIGURATION + SERVICE SERVICE Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 181: Figure 96. Home Screen

    NOTE Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. The Home Screen buttons open various information and control screens: Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 182: Figure 97. Main Menu And Power Maps Screen (Online Mode)

    Figure 97. Main Menu and Power Maps Screen (Online Mode) See Output KVA figure. See Average Efficiency figure. Consumption figure. Touching the LOAD kVA button displays the Output kVA screen shown in Figure Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 183: Figure 98. Output Kva Screen From Home Screen

    Touching the AVERAGE EFFICIENCY button displays the system efficiency screen shown in Figure Figure 99. Average Efficiency Screen from Home Screen Touching the CONSUMPTION button displays the screen in Figure 100. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 184: Figure 100. Consumption Screen From Home Screen

    Touching any of the buttons on the right side of the screen takes the user directly to that information screen. Figure 101. Bypass Screen See Output kVA figure. See Average Efficiency figure. Consumption figure. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 185: Figure 102. Typical Command Confirmation Screen (Charger Off)

    24 hours, 7 days, 30 days, or 1 year. This is true of all the meters screens listed in the top section. Figure 103. Meters Summary Screen See Average Efficiency Figure See Consumption Figure Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 186: Figure 104. Meters Selection Buttons (Typical)

    Line to Neutral Metering Method. Input Meters Screen Figure 105 shows the Input Meters screen. This screen displays the individual phase and total power values of the system. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 187: Figure 105. Input Meters Screen

    UPS Operating Instructions Figure 105. Input Meters Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 188: Figure 106. Select Source Screen

    The Show Details button Figure 107 shows the Input Meters detail screen. This screen displays the individual values of the system in additional detail. Figure 107. Input Meters Detail Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 189: Figure 108. Online Mode Metering Method Option Screen

    Figure 108. Online Mode Metering Method Option Screen Bypass Meters Screen The Bypass Meters Screen shown in Figure 109 displays values pertaining to the Bypass conditions. Figure 109. Bypass Meters Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 190: Figure 110. Bypass Mode Metering Method Option Screen

    The Show Details button on the Bypass Mode Metering Method Option Screen allows the operator to select the metering method for either line-to-line or line-to-neutral monitoring values. See Figure 110. Figure 110. Bypass Mode Metering Method Option Screen Indicates an Event (System on Bypass) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 191: Figure 111. Output Meters Screen

    7 7 . . 3 3 . . 9 9 B B a a t t t t e e r r y y M M e e t t e e r r s s S S c c r r e e e e n n Figure 112 shows the Battery Meters basic screen. Figure 112. Battery Meters Screen Eaton ® Power Xpert ®...
  • Page 192: Figure 113. System Events Screen

    Each window shows five events. The operator can also use the UP/DOWN arrows above and below the blue field (2) showing the number of events in the log. See Figure 114. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 193: Figure 114. User Log Screen

    Selecting an event opens the Event Detail screen shown in Figure 115. This screen details the specifics of the event for the user to see. Figure 115. User Log Detail Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 194: Figure 116. Battery Log Screen

    Battery Log access screen. Figure 116. Battery Log Screen Figure 117 shows the Battery Log Detail screen. Figure 117. Battery Log Detail Figure 118 shows the Battery Log Summary screen. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 195: Figure 118. Battery Log Summary Screen

    In addition, the screen displays the current status of the UPS, indicates whether the UPS is in Maintenance Bypass or Bypass, and displays the state of the UPM. Figure 119 shows the System Status screen. Figure 119. System Status Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 196: Figure 120. Load Off Button

    Figure 121. Module Controls Screen POWER XPERT 9395P Online UPM 1 UPM 1 Shutdown UPM 2 UPM 2 Not Installed UPM 3 UPM 3 Not Installed UPM 4 UPM 4 Active Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 197: Figure 122. Module Control Detail Screen

    The color of the UPM button indicates status: • Green – Active • Gray – Idle • Black – Shutdown Figure 122. Module Control Detail Screen POWER XPERT 9395P Online UPM Status UPM Power Status Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 198: Figure 123. Settings Screen

    7 7 . . 3 3 . . 1 1 5 5 C C o o n n f f i i g g u u r r a a t t i i o o n n O O p p t t i i o o n n s s S S c c r r e e e e n n The screen shown in Figure 124 allows the operator to affect changes to various system values. Figure 124. Configuration Options Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 199: Figure 125. Energy Advantage Architecture (Eaa) Screen

    Figure 125. Energy Advantage Architecture (EAA) Screen The screen shown in Figure 126 asks the operator to verify disabling the ESS mode running at that time. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 200: Figure 126. Disable Ess Screen

    Figure 126. Disable ESS Screen The screen shown in Figure 127 asks the operator if they want to start the High Alert mode timer. Figure 127. High Alert Timer Screen Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 201: Figure 128. Statistics Basic Screen

    7 7 . . 3 3 . . 1 1 8 8 E E S S S S C C o o m m p p a a r r i i s s o o n n S S c c r r e e e e n n The screen shown in Figure 130 allows the operator to visually obtain EAA mode efficiency values. Eaton ® Power Xpert ®...
  • Page 202: Figure 130. Ess Comparison Screen

    7 7 . . 3 3 . . 2 2 0 0 S S y y s s t t e e m m O O v v e e r r v v i i e e w w S S c c r r e e e e n n The screen shown in Figure 132 displays values for all UPS and UPM parameters. Eaton ® Power Xpert ®...
  • Page 203: Figure 132. System Overview Screen

    *Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see Figure 91). *Verify that input breaker CB1 is open. Close the UPS input feeder circuit breaker. Close the UPS Bypass input feeder circuit breaker. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 204 To enable Energy Saver System mode: NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 205 To disable Energy Saver System mode: NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 206 UPS Operating Instructions NOTE 1 The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 207 Figure 121. 11. On the System Status screen, select the Go to Bypass button. Select Yes on the confirmation screen. The critical load is immediately supplied by the bypass source, in Bypass mode. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 208 16. Repeat the procedures from step 13 to step 15 to start the other UPMs if required. NOTE To transfer to Online mode after starting individual UPMs, follow the procedure in paragraph 7.4.12 Transfer from Bypass to Online Mode. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 209 16. To transfer the UPM to Online mode, select the Go to Normal button under the Power Status section. • The UPM 1 Power Status shows Active • The UPM 1 status bar shows in a green color (Active) Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 210 7 7 . . 4 4 . . 1 1 4 4 S S i i n n g g l l e e U U P P M M S S h h u u t t d d o o w w n n To shut down a single UPM: Eaton ®...
  • Page 211 122). Select Start Charger. The charger status shows Charger On. To turn the battery charger off: Make sure you are logged in for user access (see Figure 95). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 212 A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this switch to control the UPS output. The REPO switch de–energizes the critical load and powers down the UPS immediately, without asking for verification. The UPS, including Bypass, remains off until restarted. Eaton ® Power Xpert ®...
  • Page 213 à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 214: Figure 133. Repo Operation

    10. Make sure you are logged in for user access (see Figure 95). 11. Press the Controls button on the Home screen (see Figure 96). The System Status screen is displayed (see Figure 119). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 215 To enable Energy Saver System mode: NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 216 To enable Variable Module Management System mode: NOTE 1 The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 217 To disable Variable Module Management System mode: NOTE 1 The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE 2 The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 218 Unfasten the front door latches and swing the doors open on all of the UPSs (see Figure 24). NOTE *Only perform steps 2 and 5 if the UPSs have input breakers CB1 (see Figure 91). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 219 Unfasten the front door latch and swing the door open (see Figure 24). NOTE *Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see Figure 91). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 220 On the System Status screen, select Go to Bypass. Select Yes on the confirmation screen. All of the UPSs transfer to Bypass mode and the critical load is immediately supplied by the bypass source. If the bypass source is not available, the power module remains on and an alarm sounds. Eaton ® Power Xpert ®...
  • Page 221 UPM "x" IS SHUTTING DOWN message appears The UPM POWER STATUS shows Idle on the Module Control Detail screen, (see Figure 122). The UPM status bar shows in a gray color (Idle). Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 222 The input, output, battery, and bypass backfeed contactors open, and the power module is turned off on the UPS being shut down. Logic power remains on. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker. Eaton ® Power Xpert ®...
  • Page 223 The UPM status bar shows in a gray color (Idle). NOTE The shutdown UPM button must be pressed twice to fully shutdown the UPM. Repeat step 4. Verify the following: UPM "x" IS SHUTTING DOWN message appears Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 224 12. Verify the External Communications Failure alarm has cleared and no other alarms are active on the online UPSs. 13. On the System Status screen, select Go Online. The Go Online? confirmation screen appears. Select Yes on the confirmation screen. Eaton ® Power Xpert ®...
  • Page 225 96). The System Status screen is displayed (see Figure 119). Select the Module Controls Detail screen for the applicable UPM charger stop (see Figure 122). Select Stop Charger. The charger status shows Charger Off. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 226 7 7 . . 5 5 . . 2 2 2 2 U U s s i i n n g g t t h h e e R R e e m m o o t t e e E E m m e e r r g g e e n n c c y y P P o o w w e e r r - - o o f f f f S S w w i i t t c c h h NOTE This procedure applies to the Eaton REPO switch installed in 4.10 Installing a REPO Switch.
  • Page 227 NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 228: Figure 134. Repo Operation

    UPS Operating Instructions Figure 134. REPO Operation Activated Deactivated Pushbutton locked into place Unlock pushbutton to release Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 229: Figure 135. Optional X-Slot Cards

    Supervisory Contact Module II (SCM II) to the UPS. LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, contact an Eaton service representative (see section 1.8 1.8 For More Information).
  • Page 230 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 231 The software’s mass configuration capabilities make installation and maintenance easy, which minimizes the effort required and benefits the bottom line. Eaton’s cost effective Intelligent Power Software manages up to ten devices at no charge, with licences for up to 100 devices – or even an unlimited number – also available.
  • Page 232: Figure 136. Remote Monitor Panel Ii

    The RMP II can be flush–mounted or surface–mounted on a desktop, or secured to a wall. Figure 136 shows an RMP II. Figure 136. Remote Monitor Panel II Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 233: Table 42. Rmp Ii Status Indicators

    SHUTDOWN IMMINENT The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 234: Figure 137. Relay Interface Module Ii

    Contacts are closed when approximately two minutes of battery time is remaining before the critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 235: Figure 138. Supervisory Contact Module Ii

    TB2–7 through TB2–9 BYPASS NOT AVAILABLE TB2–10 through TB2–12 ON BATTERY TB2–13 through TB2–15 UPS ALARM TB2–16 through TB2–18 ON BYPASS TB2–19 through TB2–21 SHUTDOWN IMMINENT TB2–22 through TB2–24 Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 236 Communication Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 237 THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative.
  • Page 238: Table 45. Ups Filter Sizes

    Ensure the UPS is in Online mode (Online status indicator is illuminated). If an alarm lamp is illuminated or the Online status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
  • Page 239: Figure 139. Isbm Section Air Filter Locations - Continuous Static Switch

    If opened, close the front door and secure the latch. Figure 139. ISBM Section Air Filter Locations – Continuous Static Switch UPM Air Filter Location ISBM Air Filter Location Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 240: Figure 140. Fi-Upm Air Filter Location

    The FI-UPM filter size is 20" x 44" x 0.25". Contact an Eaton service representative for a replacement filter. To remove the filter: Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton ®...
  • Page 241: Figure 141. Fi-Upm Air Filter Location

    9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
  • Page 242 M M a a i i n n t t e e n n a a n n c c e e T T r r a a i i n n i i n n g g A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance.
  • Page 243 The UPS is available in 50 or 60 Hz with various output power ratings. Models Power Rating Frequency Eaton 9395P-900/900* (three or four UPM) 900 kVA, 900 kW 50/60 Hz 900 kVA, 825 kW Eaton 9395P-900/900 (three or four UPM)
  • Page 244 110% for 10 minutes 125% for 120 seconds 150% for 15 seconds NOTE The 125% and 150% overloads are based on the non-derated hardware capability of the UPS. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 245 Meets IEC 62040-2, category C3 Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage Electrostatic Discharge (ESD) Immunity and with no disturbance or adverse effect to the critical load. Eaton ® Power Xpert ® 9395P-900 Installation and Operation Manual 164000501—Rev 12...
  • Page 246 16400050112 164000501 12...