Table 6- 24
Status of P0810
Status of P0811
The CDS that is
current active is
gray.
Selected
parameter index
Examples
Note
Command data sets can be switched in the "ready for operation" and "operation" state. The
switchover time is approx. 4 ms.
Table 6- 25
Parameter
P0810 = ...
P0811 = ...
r0050
A copy function is available making it easier to commission more than one command data set:
P0809.0 = ...
P0809.1 = ...
P0809.2 = 1
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the List Manual.
SINAMICS G110D
Operating Instructions, 2009-05-15, A5E02385577A AB
6.5 Changing over the command data sets (manual, automatic)
Command data set changeover using parameters P0810 and P0811.
0
0
0
Fieldbus as setpoint
source:
The speed setpoint is
specifed via the fieldbus.
Fieldbus as command
source:
The motor is switched
on/off via the fieldbus.
Parameters for switching the command data sets:
Description
1st control command for switching the command data sets
Example: When P0810 = 722.0, the system switches from command data set 0 to
command data set 1 via digital input 0.
2nd control command for switching the command data sets
Displaying the number of the CDS that is currently active
Number of the command data set to be copied (source)
Number of the command data set to which the data is to be copied (target)
Start copying
1
0
1
Analog input as setpoint
source:
The speed setpoint is
specifed via an analog
input.
Digital inputs as
command source:
The motor is switched
on/off via digital inputs.
Functions
0 or 1
1
2
-
-
99