Appendix A
A.1 Electromagnetic compatibility
Harmonic Currents
The harmonic current emissions from the SINAMICS G110 D inverters is as follows:
Table A- 3
Rating
FSA ... FSC
(400 V, 0.75 kW ... 7.5 kW)
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance before connection to the public low-voltage power supply network. Please
contact your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
EMC Immunity
The SINAMICS G110 D inverters have been tested in accordance with the immunity
requirements of category C3 (industrial) environment:
Table A- 4
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency
Electromagnetic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
Mains Interruptions & Voltage
Dips
Voltage Distortion
182
Harmonic Currents
Typical Harmonic Current (% of rated input current)
5th
73
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 61000-2-4
Class 3
7th
11th
13th
52
25
23
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80 % AM at 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80 % AM at 1 kHz
100 % dip for 3 ms
30 % dip for 10 ms
60 % dip for 100 ms
95 % dip for 5000 ms
10 % THD
Operating Instructions, 2009-05-15, A5E02385577A AB
17th
19th
23rd
22
15
12
Performance
Criterion
A
A
A
A
A
C
C
C
C
A
SINAMICS G110D
25th
10