Functions
6.11 Operation in fieldbus systems
Figure 6-36
Serial data transfer
The CTT2 protocol allows both cyclic and acyclic serial data to be transferred between
master and slave. The commands implemented to achieve this are as shown in the table
below.
Table 6- 60
CCT2 commands
Code (dec)
Code (hex)
0
0x00
1
0x01
16
0x10
80
0x50
144
0x90
17
0x11
81
0x51
145
0x91
18
0x12
82
0x52
146
0x92
19
0x13
83
0x53
147
0x93
29
0x1D
93
0x5D
157
0x9D
152
PWE component structure
Command/Response
Read cyclic data from slave
Write cyclic data to slave
Standard read request
Standard read response ok
Standard read response error
Standard write request
Standard write response ok
Standard write response error
Vendor specific read request
Vendor specific read response ok
Vendor specific read response error
Vendor specific write request
Vendor specific write response ok
Vendor specific write response error
Vendor specific exchange request
Vendor specific exchange response ok
Vendor specific exchange response error
Followed by
4 byte PWE data
4 byte PWE data
Index, length
Data
Standard error code
index, length, data
Standard error code
index, length
data
error object
Index, length, data
error object
index, read length, write
length, write data
read data
error object
Operating Instructions, 2009-05-15, A5E02385577A AB
SINAMICS G110D