Startup

Only two steps are necessary for a Quick Setup (see page 21 for detailed instructions):
1.
Use the hand programmer to set the PROFIBUS address locally.
2.
Use SIMATIC PDM to calibrate the four set points: High and Low Calibration Point,
and High and Low Level Point.
SITRANS LR 200 automatically starts up in RUN mode and detects the material level. The
LCD displays the material level referenced from the Low Level Point
Analog Input Function Block 1/AIFB1). System status is displayed on the LCD, or on a
remote communications terminal.
Note:
SITRANS LR 200 (PROFIBUS PA) continues to monitor in and out values even
when the device is in PROGRAM mode.

Startup Display (RUN mode)

Normal operation
2
3
1
7
1 – Primary region displays material level (Output of the active AIFB)
2 – Menu number (displays the number of the active AIFB: 1 or 2)
3 – Echo status indicator: Reliable Echo
(The Unreliable Echo border flashes if LOE is pending
becomes active, the border is solid and the text region displays S: 0.)
4 – Bar graph border (always visible in RUN mode)
5 – Units or Percent
6 – Active bar graph represents material level
(The lowest bar flashes once per second as a heartbeat.)
7 – Secondary region displays one of the following:
• Internal electronics temperature
• Value representing echo confidence
• Distance (Secondary Value 2)
• General status information, or a fault code
1.
Calibration
See
2.
Loss of Echo (LOE)
Please see
3.
For a list of fault codes, their meanings, and corrective actions, please see
Extended Diagnostics (General Fault Codes)
Page 16
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
2
3
4
5
6
on page 22 for an illustration.
on page 34, for more details.
Failsafe operation
3
2
7
or Unreliable Echo
3
on page 29.
1
(the output of
5
6
2
. When LOE
Acyclic
7ML19985HP01