Using Auto False Echo Suppression; Level Application Example - Siemens SITRANS LR200 Instruction Manual

Hide thumbs Also See for SITRANS LR200:
Table of Contents

Advertisement

Calibration – steps 1 to 7
1.
Open the menu Device – Sensor Calibration and select the button Dry Calibration
(Click on Additional Information to see the schematic showing the PROFIBUS
parameters.)
2.
Enter the new value for Low Calibration Point (default units are meters).
3.
Enter the corresponding value for Low Level Point in percent (default is 0).
4.
Enter the new value for High Calibration Point (default units are meters).
5.
Enter the corresponding value for High Level Point in percent (default is 100).
6.
Click on Transfer.
7.
SITRANS LR 200 is now ready to operate.

Using Auto False Echo Suppression

If SITRANS LR 200 displays a false high level, or the reading is fluctuating between the
correct level and a false high level, you can use the Auto False Echo Suppression
parameters to prevent false echo detection. See
setup
on page 100 for instructions.

Level application example

If volume conversion is not selected, Primary Value (PV) will be level (SV1). SV1 is the sum
of level plus level offset (if any).
Level Units:
High Level
Point = 100%
Low Level Point
= 0%
1.
The "wet calibration" process is not recommended for SITRANS LR 200 (PROFIBUS PA).
2.
For standard configuration reference point, please see
on page 13. For other configurations, see
44 onwards.
7ML19985HP01
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
2
Sensor Value
SV2
Level
Level
Offset
(if
any)
Secondary Value 1
TVT (Auto False Echo Suppression)
Sensor Units:
Sensor Offset
Near
Range
High
Calibration
Point = 3 m
Low
Calibration
Point = 5 m
SITRANS LR 200 Dimensions
Appendix D: Flange Adapter Versions
1
.
Sensor Reference
2
Point
Far Range
, page
Page 23