Fm/Csa - Siemens SITRANS LR200 Instruction Manual

Hide thumbs Also See for SITRANS LR200:
Table of Contents

Advertisement

FISCO-Concept
Note:
For complete details and instructions regarding the FISCO Concept, see page 111
for drawing number 23650529, also available from the product page of our website:
www.siemens.com/processautomation.
The FISCO Concept allows interconnection of intrinsically safe apparatus to associated
apparatus not specifically examined in such combination. The criteria for interconnection
is that the voltage (Ui or Vmax), the current (Ii, or Imax) and the power (Pi, or Pmax) which
intrinsically safe apparatus can receive and remain intrinsically safe, considering faults,
must be equal to or greater than the voltage (Uo or Voc or Vi), the current (lo or Isc or li),
and the power (Po or Pmax) levels which can be delivered by the associated apparatus,
considering faults and applicable factors. In addition, the maximum unprotected
capacitance (Ci) and inductance (Li) of each apparatus (other than the termination)
connected to the fieldbus must be less than or equal to 5 nF and 10 µH respectively.
In each segment only one active device, normally the associated apparatus, is allowed to
provide the necessary energy for the fieldbus system. The allowed voltage Uo (or Voc or
Vt) of the associated apparatus is limited to the range of 14V dc to 24V dc. All other
equipment connected to the bus cable has to be passive, meaning that they are not
allowed to provide energy to the system, except to a leakage current of 50 µA for each
connected device. Separately powered equipment needs a galvanic isolation to assure
that the intrinsically safe fieldbus circuit remains passive.

FM/CSA

Approved dust-tight and water-tight conduit seals are required for outdoor
NEMA 4X / type 4X / NEMA 6, IP67, IP68 locations.
The maximum voltage of the non-intrinsically safe apparatus must not exceed 250 V
rms.
PLC (active)
Non-hazardous Area
Hazardous Area
Zone 0, 1,
or 2
Page 108
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
EEx ia
PDM
EEx ia type DP/
PA coupler
7ML19985HP01

Advertisement

Table of Contents
loading