Quick Setup

Activating SITRANS LR 200

Note:
Keep infrared devices such as laptops, cell phones, and PDAs, away from
SITRANS LR 200 to prevent inadvertent operation.
Power up the instrument. SITRANS LR 200 starts in RUN mode, and the LCD displays the
output of AIFB1.

Setting the PROFIBUS address via the hand programmer

Notes:
• Local programming must be enabled, to allow changes (see
on page 20).
• CLEAR
can be used to clear the field.
C
• Press Right ARROW
• Press Left ARROW
PROGRAM icon is not visible).
1.
Press Mode
and open Menu level 1.
2.
Press Right ARROW
PROFIBUS address.
3.
Press Right ARROW
mode: the PROGRAM icon will flash.
4.
Key in a new value and press Right ARROW
to accept it.
The LCD displays the new value; PROGRAM icon
disappears, and the last menu digit flashes to
indicate Navigation mode.
5.
Press Mode
1.
Default address is 126.
7ML19985HP01
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
to open Edit mode: the PROGRAM icon flashes.
to cancel Edit mode: the Menu number flashes (the
to activate PROGRAM mode
twice to navigate to
again to open Edit
to return to RUN mode.
1
Local operation enable
Menu level: last
digit flashes in
Navigation mode.
Program icon:
flashes in Edit
mode.
Right-most digit
flashes in
Navigation
mode.
Page 21