Siemens SITRANS LR200 Instruction Manual page 95

Hide thumbs Also See for SITRANS LR200:
Table of Contents

Advertisement

2.2.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target
12
range.
Related
para-
meters
Values
Note:
Changing Response Rate resets the following parameters: LOE Timer,
Fill Rate, Empty Rate, and Echo Lock.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy: faster settings allow for more
level fluctuation.
2.2.3. Echo Lock
Note:
Ensure the agitator is always running while SITRANS LR 200 is
monitoring the vessel, to avoid stationary blade detection.
Selects the measurement verification process.
Values
Related
parameters
If a material agitator or mixer is used in the monitored vessel, Echo Lock should
be set for Maximum Verification or Material Agitator to avoid agitator blade
detection.
1.
For more detail, see
2.
For more detail, see
7ML19985HP01
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
Response
LOE Timer
Rate
(minutes)
1 * slow
100
2
medium
10
3
fast
1
0
Off
1
Maximum Verification
2
*
Material Agitator
3
Total Lock
Maximum Fill Rate
Maximum Empty Rate
Echo Lock Sampling
Echo Lock Window
Algorithm
LOE Timer
on page 34.
Echo Lock
on page 34.
1
Empty
Fill Rate
Rate
0.1 m/minute 0.1 m/minute
1 m/minute
1 m/minute
10 m/minute 10 m/minute
Echo
2
Lock
material
2
agitator
Page 89