Quick Start Guide - Baldor 23H Series Installation & Operating Manual

Ac servo control
Hide thumbs Also See for 23H Series:
Table of Contents

Advertisement

Section 1

Quick Start Guide

Overview
Quick Start Checklist
MN723
If you are an experienced user of Baldor controls, you are probably already familiar with
the keypad programming and keypad operation methods. If so, this quick start guide has
been prepared for you. This procedure will help get your system up and running in the
Keypad mode quickly. This will allow motor and control operation to be verified. This
procedure assumes that the control, motor and dynamic brake hardware are correctly
installed (see Section 3 for procedures) and that you have an understanding of the
keypad programming & operation procedures. It is not necessary to wire the terminal
strip to operate in the keypad mode (Section 3 describes terminal strip wiring
procedures). The quick start procedure is as follows:
1.
Read the Safety Notice and Precautions in section 2 of this manual.
2.
Mount the control. Refer to Section 3 "Physical Location" procedure.
3.
Connect AC power, refer to Section 3 "Three Phase Motor and Control
Connections".
4.
Connect the motor, refer to Section 3 "Three Phase Motor and Control
Connections".
5.
Connect the resolver, refer to Section 3 "Resolver Feedback".
6.
Install dynamic brake hardware, if required. Refer to Section 3 "Optional
Dynamic Brake Hardware".
7.
Connect the keypad to the keypad connector of the main control board. Refer
to Section 3 "Keypad Installation Procedure".
Check of electrical items.
CAUTION: After completing the installation but before you apply power, be
sure to check the following items.
1.
Verify AC line voltage at source matches control rating.
2.
Inspect all power connections for accuracy, workmanship and torque as well as
compliance to codes.
3.
Verify control and motor are grounded to each other and the control is
connected to earth ground.
4.
Check all signal wiring for accuracy.
5.
Be certain all brake coils, contactors and relay coils have noise suppression.
This should be an R-C filter for AC coils and reverse polarity diodes for DC
coils. MOV type transient suppression is not adequate.
WARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
Check of Motors and Couplings
1.
Verify freedom of motion of the motor shaft.
2.
Verify that all motor couplings are tight without backlash.
3.
Verify the holding brakes if any, are properly adjusted to fully release and set to
the desired torque value.
Quick Start Guide 1-1