Section 3
Receiving & Installation
Receiving & Inspection

Physical Location

C, C2, D, D2, E, and F
MN723
When you receive your control, there are several things you should do immediately.
1.
Observe the condition of the shipping container and report any damage
immediately to the commercial carrier that delivered your control.
2.
Verify that the part number of the control you received is the same as the part
number listed on your purchase order.
3.
If the control is to be stored for several weeks before use, be sure that it is
stored in a location that conforms to published storage temperature and
humidity specifications. (Refer to Section 7 of this manual).
The mounting location of the control is important. It should be installed in an area that is
protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic
particles, shock and vibration.
Several other factors should be carefully evaluated when selecting a location for
installation:
1.
For effective cooling and maintenance, the control should be mounted vertically
on a flat, smooth, non-flammable vertical surface. Table 3-1 lists the Watts
Loss ratings for enclosure sizing.
2.
At least two inches clearance must be provided on all sides for air flow.
3.
Front access must be provided to allow the control cover to be opened or
removed for service and to allow viewing of the Keypad Display.
Controls packaged in a floor mounted enclosure must be positioned with
clearance to open the enclosure door. This clearance will also provide
sufficient air space for cooling.
4.
Altitude derating. Up to 3300 feet (1000 meters) no derating required. Above
3300 ft, derate the continuous and peak output current by 2% for each 1000 ft.
5.
Temperature derating. Up to 40°C no derating required. Above 40°C, derate
the continuous and peak output current by 2% per °C. Maximum ambient is
55°C.
Table 3-1 Series 23H Watts Loss Ratings
Enclosure Size
A, B and B2
G
230 VAC
2.5KHz
8.0KHz
PWM
PWM
14 Watts/
17 Watts/
Amp
Amp
12 Watts/
15 Watts/
Amp
Amp
460 VAC
2.5KHz
8.0KHz
PWM
PWM
17 Watts/
26 Watts/
Amp
Amp
15 Watts/
23Watts/
Amp
Amp
15 Watts/
Amp
Receiving & Installation 3-1