Table 3-3 460VAC Controls (3 Phase) Wire Size and Protection Devices
Control Output Rating
Amps
2
2
4
5
8
11
14
21
27
34
40
52
65
77
96
124
Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control
output current and no harmonic current.
MN723
Input Breaker
(Amps)
HP
0.75
1
2
3
5
7.5
10
15
30
20
40
25
50
30
50
40
70
50
90
60
100
75
125
100
175
Input Fuse (Amps)
Fast Acting
Time Delay
2
2
3
2.5
6
5
8
7
12
10
20
15
25
20
30
25
40
35
50
45
60
50
80
70
100
90
125
100
150
125
200
175
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
3.31
10
5.26
10
5.26
8
8.37
8
8.37
6
13.3
4
21.2
3
26.7
2
33.6
1/0
53.5
Receiving & Installation 3-7