Opto-Isolated Outputs

24Com
Optional
Customer
Supplied
Relays &
Diodes
Using Internal Supply
(Sinking the Relay Current)
-
Optional Customer Supplied
10VDC to 30VDC Source
+
Optional
Customer
Supplied
Relays &
Diodes
Using External Supply
(Sinking the Relay Current)
3-38 Receiving & Installation
Four programmable opto isolated outputs are available at terminals J1-19 through J1-22.
See Figure 3-44. Each output may be programmed to represent one output condition.
The output conditions are defined in Section 4 of this manual.
The opto isolated outputs may be configured for sinking or sourcing 60 mA each, as
shown in Figure 3-44. However, all must be configured the same. The maximum voltage
from opto output to common when active is 1.0 VDC (TTL compatible). The equivalent
circuit for the opto isolated outputs is shown in Figure 3-45.
If the opto outputs are used to directly drive a relay, a flyback diode rated at 1A, 100 V
(IN4002 or equivalent) minimum should be connected across the relay coil.
Each opto output is programmed in the Output programming block.
Figure 3-44 Opto-isolated Output Configurations
+24VDC
17
39
18
19
41
20
42
21
43
22
44
Optional Customer Supplied
10VDC to 30VDC Source
17
39
18
19
41
20
42
21
43
22
44
See recommended terminal tightening torques in Section 7.
24Com
17
18
19
20
21
22
Using Internal Supply
(Sourcing the Relay Current)
-
17
+
18
19
20
21
22
Using External Supply
(Sourcing the Relay Current)
+24VDC
39
41
42
Optional
Customer
43
Supplied
Relays &
44
Diodes
39
41
42
Optional
Customer
43
Supplied
Relays &
44
Diodes