Size D2 Single Phase Power Installation

J100
Pins 1 & 2 = Three Phase
Pins 2 & 3 = Single Phase
Figure 3-11 Size D2 Single Phase 230/460VAC Power Connections
L1
Note 1
* Circuit
Breaker
Note 3
A1
B1
*Optional
Note 4
Line
Reactor
A2
B2
Note 3
L1
Control
3-14 Receiving & Installation
Jumper Configuration
Locate the Interface board, and place J100 on pins 2 & 3 for single phase operation.
Figure 3-10
L2
Earth
Note 2
* Optional components not provided with control.
Notes:
L2
L3
1.
2.
Baldor
3.
4.
(see Figure 3-11)
Jumper Configuration
J100
1
2
3
L1
L2
* Fuse
Connection
A1
B1
See "Protective Devices" described previously in this section.
Use same gauge wire for Earth ground as is used for L1, L2 and L3.
Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
Note 1
MN723