Table 3-4 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls*
Control Output Rating
Amps
6.9
8.0
12
17
28
40
50
68
88
110
136
176
216
Table 3-5 Single Phase Rating Wire Size and Protection Devices - 460 VAC Controls*
Control Output Rating
Amps
3.5
4.0
6.0
8.5
14
20
25
34
44
55
68
88
108
*Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control
output current and no harmonic current.
3-10 Receiving & Installation
Table 3-4 and 3-5 list the wire size for the input AC power wires. Motor leads should be
sized from the 3 phase tables
Input Breaker
Input Breaker
HP
(Amps)
0.75
1
2
3
5
7.5
10
70
15
90
20
110
25
150
30
175
40
225
50
275
Input Breaker
Input Breaker
HP
(Amps)
0.75
1
2
3
5
7.5
10
15
45
20
60
25
70
30
90
40
110
50
150
.
Input Fuse (Amps)
Fast Acting
Time Delay
10
9
12
10
20
17.5
25
25
45
35
60
50
80
70
110
90
150
125
175
150
200
175
250
250
350
300
Input Fuse (Amps)
Fast Acting
Time Delay
5
5
6
5.6
10
8
15
12
20
20
30
25
40
30
50
45
70
60
80
70
100
90
150
125
175
150
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
12
3.31
10
5.26
8
8.37
6
13.3
4
21.2
3
26.7
2
33.6
1/0
53.5
3/0
85.0
(2) 1/0
(2) 53.5
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
14
2.5
12
3.31
10
5.26
10
5.26
8
8.37
8
8.37
6
13.3
4
21.2
3
26.7
2
33.6
MN723