Resolver Feedback - Baldor 23H Series Installation & Operating Manual

Ac servo control
Hide thumbs Also See for 23H Series:
Table of Contents

Advertisement

Table 3-7 Dynamic Brake Wire Size for RGA, RBA and RTA Assemblies
Control
Braking Option
Braking Option
Voltage Rating
Watts Rating
VAC
230
<2,000
230
2,100 – 5,000
230
5,100 – 10,000
230
>10,000
460
<4,000
460
4,100 – 10,000
460
10,100 – 20,000
460
>20,000

Resolver Feedback

P
= Twisted Pair
See recommended Terminal Tightening Torques in Section 7.
3-20 Receiving & Installation
B+ / B- and R1 / R2 /
Terminals
Wire Size
AWG
16
14
10
8
16
14
10
8
The resolver connections are made at the J1 connector as shown in Figure 3-23. The
resolver cable must be shielded twisted pair #22 AWG (0.34mm
cable must also have an overall shield and not exceed 150 feet (45m) in length.
Maximum wire-to-wire or wire-to-shield capacitance is 50pf per foot (maximum of 7500pf
for 150 ft). See electrical noise considerations in Section 5 of this manual.
Resolver wiring must be separated from power wiring. Separate parallel runs of resolver
and power cables by at least 3". Cross power wires at right angles only. Insulate or tape
ungrounded end of shields to prevent contact with other conductors or ground.
Figure 3-23 Resolver Cable Connections
R2
S2
R1
S4
S3
S1
Figure 3-24 Baldor Resolver Cable Lead Identification
2
mm
Volt
1.31
600
2.08
600
6
600
10
600
1.31
600
2.08
600
6
600
10
600
J1
P
23
24
P
25
26
P
27
28
Red
EXCITATION+
Blue
EXCITATION–
Green
COSINE+
Shield
EXCITATION–
Yellow
COSINE–
Pink
SINE+
Gray
SINE–
D1 / D2 /
Terminals
Wire Size
2
AWG
mm
20-22
0.5
20-22
0.5
20-22
0.5
20-22
0.5
20-22
0.5
20-22
0.5
20-22
0.5
20-22
0.5
2
) wire minimum. The
SINE+
SINE–
COSINE+
COSINE–
EXCITATION +
EXCITATION –
Volt
600
600
600
600
600
600
600
600
MN723