Assembling Dc Cable To Connector - Sungrow SG3KTL-EC User Manual

3g grid-connected inverter
Table of Contents

Advertisement

User Manual
Prior to connecting the inverter to PV inputs, the following electrical specifications
must be met simultaneously:
Total DC Power
Type
Limit for Inverter
SG3KTL-EC
3191 W
SG4KTL-EC
4255 W
SG5KTL-EC
5265 W
SG6KTL-EC
6312 W

5.5.2 Assembling DC Cable to Connector

All DC cables are equipped with water-proof direct plug-in connectors, which match
the DC terminals at the bottom of the inverter.
The positive and negative connectors are marked with polarity symbols
and should be equipped with correctly colored cables.
e.g. Red cable should be connected with DC positive terminal while the
blue one should be connected with the negative.
DC Cable Requirements
Type
Cross-Section
Area Range
4...6 mm
SG3KTL-EC
12AWG-10AWG
4...6 mm
SG4KTL-EC
12AWG-10AWG
Open-circuit
Voltage Limit for
Each Input
1000 V
1000 V
1000 V
1000 V
Outer
Diameters
2
6...9 mm
2
6...9 mm
Short-circuit
Current Limit for
Total Input
24.8 A
24.8 A
24.8 A
24.8 A
Cable
Max.
Withstand
Voltage
1000 V
1000 V
5 Electrical Connection
Max.
Withstand
Current
Same
with
short-circuit
current.
Same
with
short-circuit
current.
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sg5ktl-ecSg6ktl-ecSg4ktl-ec

Table of Contents