Assembling Dc Cable To Connector - Sungrow SG2KTL-S User Manual

Pv grid-connected inverter
Hide thumbs Also See for SG2KTL-S:
Table of Contents

Advertisement

User Manual
Total DC Input
Type
Power Limit
SG2KTL-S
2300W
SG2K5TL-S
2800W
SG3KTL-S
3300 W

5.5.2 Assembling DC Cable to Connector

All DC cables are equipped with water-proof direct plug-in connectors, which match
the DC terminals at the bottom of the inverter.
The positive and negative connectors are marked with polarity symbols
and should be equipped with correctly colored cable.
e.g. Red cable should be connected with DC positive terminal while the
blue one be connected with the negative.
DC Cable Requirements
Type
SG2KTL-S/SG2K5TL-S/
SG3KTL-S
SG3K6TL-S/SG4KTL-S
SG3KTL-D/SG3K6TL-D
/SG4K6TL-D/SG5KTL-D
Open-circuit
Voltage Limit
600V
600V
600V
Cross-Section
Outer
Area Range
Cable
Diameters
2
2.5...6mm
5...8mm
2
2.5...6mm
5...8mm
2
2.5...6mm
5...8mm
5 Electrical Connection
Short-circuit
Current Limit
12A
12A
12A
Max.
Max.
Withstand
Withstand
Voltage
Current
Same with
600 V
short-circuit
current.
Same with
600 V
short-circuit
current.
Same with
600 V
short-circuit
current.
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents