Sungrow SG3KTL-EC User Manual page 69

3g grid-connected inverter
Table of Contents

Advertisement

User Manual
3.
Country
Perform country settings with the right two
buttons. Detailed button functions can be
found in "10.1 Description of Button
Function". Press
Confirm the settings by Pressing ENTER.
Refer to "10.9.2 Selecting the Country Code" for country code explanation. If
the inverter is installed where the country code is not included, please choose
the item "Other" and manually set the protective parameters.
If the country code is not set correctly during commissioning, reset the
protective parameters as dictated in "10.9.2 Selecting the Country Code" .
There may be faults if otherwise.
(Optional) When the country code "AU" is selected, Press
4.
enter the "Grid Standard" interface. Press
standard. Press
5.
(Optional) When the country code "AU" and the grid standard "Manual"
are selected, Press
choose the correct stage. Press
time value. Confirm the settings by Pressing ENTER. The following figure
shows the settings of single-stage protection parameters.
selection
screen
to choose country code.
ENTER
to confirm the choice.
ENTER
to enter the "Pro-Stage" interface. Press
will
prompt.
/
to choose the correct grid
to move cursor and Press
Countries
Country: [
AU ]
Vgrid-max 260.0V
Vgrid-min 210.0V
Fgrid-max 52.00Hz
Fgrid-min 47.00Hz
7 Commissioning
ENTER
/
to scroll up
Grid Standard
AG
EE
EG
PN
PC
WP
Manual
Default
Pro-Stage
Single-stage
Multi-stage
to
to
59