SG3KTL-M/SG4KTL-M/SG4K6TL-M/SG5KTL-M

Quick Installation Guide

This guide provides a general instruction of the installation procedure of
SG3KTL-M/SG4KTL-M/SG4K6TL-M/SG5KTL-M.
In no case shall users open the enclosure . Loss of any or all warranty rights may follow if otherwise.
In no case shall this guide substitute for the user manual or related notes on the device.
Make sure to read over, fully understand and strictly follow the detailed instructions of the user manual and other
related regulations before installing the equipment.
Any violation could result in personal death or injury or device damage.
1
Installation Preparation
Select appropriate cables before securing the inverter to the wall.
Terminal
Type
Cross-sectional Area(mm
Range
Recommended
Value
SG3KTL-M
4...6
4
SG4KTL-M
4...6
4
AC terminals
SG4K6TL-M
4...6
6
SG5KTL-M
4...6
6
DC terminal
SG3K/4K/4K6/5KTL-M
2.5...6
-
RS485 Com. terminal
SG3K/4K/4K6/5KTL-M
Shielding Ethernet cable or shielding twist-pair type cable
PE terminals
SG3K/4K/4K6/5KTL-M
-
6
2
Mounting Inverter onto the Wall
1. Turn off the DC switch and then disconnect the
DC input
DC switch
AC circuit breaker. Prevent them from inadvertently
area
(Optional)
reconnecting during inverter installation.
* Image here is for reference only. Actual product you
receive may differ.
OFF
ON
EN-1
EN
2. Secure the backplate to the wall with the provided
mounting kits. Hang the inverter to the two recesses
Original Version
of the backplate.To protect the inverter from theft,
you can lock it to the backplate with a padlock.
• The theft protection is optional.
• You shall lock the inverter to the mounted eye plate of
the backplate with a suitable (stainless, secured shackle
and lock cylinder) padlock.
• You must ensure that the key is available at all times for
possible service purposes.
3. Allow sufficient room around the inverter to
enable unobstructed air flow during installation.
For multiple inverters installation, positionthe
inverters in staggered arrangement.
2
)
Outer cable diameter(mm)
Range
Recommended
Value
10...14
10
10...14
10
4. Plug the AC connector into AC terminal placed
10...14
10
underneath the inverter. Connect the "PE" cable
10...14
10
to the grounding electrode and connect the
5...8
-
phase cable and "N" cable to the AC circuit
breaker as shown on the right.
-
-
RS485 or WiFi
RS485
communication
communication
terminal
terminal
AC
terminal
DC1
DC2
RS485/WiFi
RS485
AC
Install backplate
Hang inverter
Mounting ear
Backplate
Inverter 1
Inverter 2
Inverter n
PV Arrays 1
PV Arrays 2
PV Arrays n
Mounting Frame of PV arrays
Copper Bus Bar
Grounding Electrode
Grounding of PV Power System
L
N
AC Circuit Breaker
Inverter
L
N
PE
AC Grounding Electrode
Grounding of Inverter AC Side
EN-2
5. The inverter is equipped with second protective earth terminal as specified in EN 50178. Users may
choose to connect PE connection.
Item
Description
A
Screw
B
Lock washer
C
Washer
D
Cable socket
E
Yellow-green cable
*The connection parts are not included in the delivery scope.
6. Check the cable polarities of PV input before PV input connection. Connect the DC plug-in connectors
to corresponding DC terminals. Connect other PV strings following the same procedures if necessary.
Unused DC terminals should be sealed.
The inverter can work on independent mode and parallel mode, you can connect PV input as shown
(In parallel mode, one pair of DC terminals in DC1 input and DC2 input must be short-circuited by
Y-type cable connector terminal.).
The PV input configuration mode should be consistent with the setting in the LCD.
Independent Mode
Parallel Mode
+
-
+
-
+
-
+
-
+
-
PV Input Specifications:
Type
Area
DC Power Limit
Total DC Input
Open-circuit Voltage
for Each Input
Power Limit
Limit for Each Input
DC1
3200W
SG3KTL-M
3200W
550V
DC2
3200W
DC1
3000W
SG4KTL-M
4300W
550V
DC2
3500W
DC1
3000W
SG4K6TL-M
4950W
550V
DC2
3500W
DC1
3000W
SG5KTL-M
5400W
550V
DC2
3500W
EN-3
Remark
M4×12mm
-
-
-
6mm
2
(9AWG)
Short-circuit Current
Limit for Each Input
12A
24A
12A
12A
32A
20A
12A
32A
20A
12A
32A
20A

Advertisement

loading

Summary of Contents for Sungrow SG3KTL-M

  • Page 1: Quick Installation Guide

    Hang the inverter to the two recesses choose to connect PE connection. Original Version of the backplate.To protect the inverter from theft, you can lock it to the backplate with a padlock. SG3KTL-M/SG4KTL-M/SG4K6TL-M/SG5KTL-M Item Description Remark Quick Installation Guide •...
  • Page 2 7. Several communication methods are Commissioning a) Connect WiFi to 5-pin terminal ▼ ▼ b) Connect RS485 to 5-pin terminal c) Connect RS485 to RJ45 terminal Only qualified personnel are allowed to adjust or configure parameters related to system protection . RS485/WIFI Button Operation...

This manual is also suitable for:

Sg4k6tl-mSg5ktl-mSg4ktl-m