Multinode connection for setup

Initial setup is performed best on a test bench. The unit is powered up and connected via
the Ethernet cable to a PC. The PC is used to access the Multinode Configuration Tool
application, which is loaded on the multinode and contains the forms where you enter the
required addresses and configuration information.
Step
1
Place the multinode/WSG on a test bench.
2
Connect the power cable leads to the proper power source (24Vdc).
If the multinode is equipped with a Red power cable:
Connect the Red wire to +24 volt dc.
Connect the Black wire to 24 volt COMMON.
If the multinode is equipped with a Grey power cable:
Connect both the Red and Green wires to +24 volt dc.
Connect both the Black and White wires to the 24 volt COMMON.
3
Power on the multinode unit.
4
Connect one end of the RJ-45 Ethernet cable labeled WAN1 to an Ethernet
port on the laptop or PC.
5
Verify these settings on your PC or set as follows:
TCP/IP properties must be set to "Using the following IP address."
IP Address: 192.168.254.1
Network Mask: 255.255.255.0
To access the screen, which contains these settings on your PC, and view or
change your TCP/IP settings:
If the operating system on your computer is Windows 2000 or XP, follow the
path Start >Settings > Network and Dialup Connections > Local Area
Connection and select the Properties button. In the Properties window,
highlight the TCP/IP protocol and click Properties. Make sure that the radio
button for Using the following IP address is selected, and enter the IP
address 192.168.254.1 and the network mask 255.255.255.0.