Addendum
OneWireless Multinode - Models WNMN and WNMS
external wiring routed through metallic conduit (via the ¾" NPT connection) and shall be
terminated within a junction rated appropriately for the conditions of the installation.
These units are non-repairable items and if faulty must be replaced. The electrical supply
must be switched off before any replacement and during any time that the wiring
terminations are being connected or disconnected.
Before commissioning of this equipment, it must be verified that the supply voltage
cannot exceed the voltage rating as identified on the product label.
The flying leads of the multinode shall be suitably protected against mechanical damage
and terminated within a terminal or junction facility suitable for the conditions of use.

Special conditions for safe use

It is the responsibility of the installer and user to ensure chemical compatibility between
the equipment with the gases and vapors to which the equipment may be exposed. The
equipment is constructed largely of the following materials:
Enclosure - Aluminum
Conduit entry - Galvanized steel
Printed Circuit Boards - FR4 epoxy-impregnated glass fiber
Wiring insulation - PVC
120
OneWireless Multinode User's Guide
R110
6/08