Reset Button; Communication Baud Rates; Connection To Honeywell Forge; Connection To Multitech Lorawan Hub - Honeywell GW-1000-WE Installation Instructions Manual

Smb gateway
Hide thumbs Also See for GW-1000-WE:
Table of Contents

Advertisement

GATEWAY (GW-1000-WE/GW-1000-NWE)

Reset Button

The GW-1000-WE/GW-1000-NWE gateway has a reset
button to reset the device to factory default. The user
should push the button for 20 seconds to reset the
Gateway. After reset, the Gateway will restart two times. The
reset performs the following operations and completes in
three minutes.
• Erases the Gateway configuration
• Resets the SSID to default
• Retains the user registration
• Retains the current firmware version
• Retains the current OS version
• LED Yellow breathing

Communication Baud Rates

Table 11. Communication Baud Rates
Ethernet
10/100/1000 Mbit/s, RJ45
BACnet MSTP
9.6, 19.2, 38.4, 76.8, 115.2 Kbps
Wi-Fi
802.11b: up to 11Mbps
802.11g: up to 54Mbps
802.11n: up to 150Mbps
Bluetooth
BR: up to 1Mbps
EDR: up to 3Mbps
BLE: up to 1Mbps
Wi-Fi Range with
100 ft
unobstructed
line of sight
Supported type
Wi-Fi Access Point - Providing
of Wi-Fi
access point to IO-10MIXR-WE/IO-
connections
10MIXR-NWE Smart IO and
TC500A-N Commercial Thermostat
devices
NOTE: Wi-Fi 5 GHz is for future use.

Connection to Honeywell Forge

GW-1000-WE/GW-1000-NWE Gateway uses HTTPS for
connecting to the Honeywell Forge platform. It connects to
Internet via Ethernet 1 port.
Connection to MultiTech LoRaWAN
Hub
GW-1000-WE/GW-1000-NWE Gateway uses UDP Port for
its communication on Wifi and Ethernet 2. For more
information, refer to "Gateway to MultiTech LoRaWAN hub
connection" section on page 10.
Small and Medium Building
Administrator Supervisor
Dashboard
For more information, refer to the Small and Medium
Building Administrator Supervisor Dashboard user guide
(31-00379M).
31-00426 | Rev.10-20

Honeywell Connect Mobile App

For more information, refer to the Small and Medium
Building Administrator Deploy App Setup guide (31-
00451M).

POWER SUPPLY

WARNING
Risk of electric shock or equipment damage!
• Do not connect more than one GW-1000-WE/GW-
1000-NWE gateways to the same transformer.

Transformers

Honeywell Transformers
A transformer can power the GW-1000-WE/GW-1000-
NWE gateway. When determining total current
consumption and selecting the appropriate transformer,
take into account the number of connected modules,
accessories, and field devices.
NOTE: In Europe, system transformer(s) must be safety
isolating transformers according to IEC61558-2-
6. In the U.S.A. and Canada, NEC Class-2 trans-
formers must be used.
Table 12. Honeywell CRT Series Transformers (Europe)
Part No.
CRT 2
220/230 Vac
CRT 6
220/230 Vac
CRT 12
220/230 Vac
Table 13. Honeywell 1450 Series Transformers
Part No.
Primary Side
14507287
-001
120 Vac
-002
120 Vac
-003
120 Vac
-004
240/220 Vac
-005
240/220 Vac
-006
240/220 Vac
NOTE: Standard commercially available transformers can
also power the GW-1000-WE/GW-1000-NWE
gateway.
8
Primary Side
Secondary Side
24 Vac, 50 VA, 2 A
24 Vac, 150 VA, 6 A
24 Vac, 300 VA, 12 A
(N. America)
Secondary Side
24 Vac, 50 VA
2 x 24 Vac, 40 VA; 100 VA
from separate
transformer
24 Vac, 100 VA; 24 Vdc;
600 mA
24 Vac, 50 VA
2 x 24 Vac, 40 VA; 100 VA
from separate
transformer
24 Vac, 100 VA; 24 Vdc,
600 mA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gw-1000-nwe

Table of Contents