3) Device Connection Order

1. Reader(s)
2. Input Device(s) (if used)
3. Output Device(s)
4. Communications
©
2013 Honeywell, Inc. www.Honeywell.com
Connect readers to terminal block per
Connection Diagram.
Connect Request to Exit Devices and/or
Door Status / Position Switch (if used) to
terminal block per Connection Diagram.
Connect Locking Device(s) and/or
Auxiliary Devices (Intrusion, Sounder,
Strobe, etc.) (if used) to terminal block
per Connection Diagram.
Connect the Controller Board to the
computer by using an Ethernet cable or a
Micro USB-B cable.
NOTE: Install USB drivers prior to
making USB connection (see Section
5.1).

4) Powering Up

1. Apply power (PoE or 12VDC power source) to panel.
2. Verify panel power up.
The PoE or PWR LED will be illuminated and there
will be a slight delay as the operating system loads.
RUN LED will initially be solid red then
steadily flash green, once per second.
3. Verify panel and wiring functionality.
Trigger any input device. STS LED should flash
BLUE briefly.
Swipe a card at any reader. RDR LED should flash
GREEN briefly.
Note: For dry-type configurations, the power supply must be voltage-
compatible, listed to UL 294 or UL 609 for UL installations and
CAN/ULC-S318 for ULC installations, and able to supply sufficient
backup power.
CONGRATULATIONS!
YOU HAVE SUCCESSFULLY POWERED UP
the NetAXS-123 Access Controller!