NetAXS-123 Startup Guide, Document 800-05780V2
3) Device Connection Order
1. Reader(s)
2. Input Device(s) (if used)
3. Output Device(s)
4. Communications
©
2013 Honeywell, Inc. www.Honeywell.com
Connect readers to terminal block per
Connection Diagram.
Connect Request to Exit Devices and/or
Door Status / Position Switch (if used) to
terminal block per Connection Diagram.
Connect Locking Device(s) and/or
Auxiliary Devices (Intrusion, Sounder,
Strobe, etc.) (if used) to terminal block
per Connection Diagram.
Connect the Controller Board to the
computer by using an Ethernet cable or a
Micro USB-B cable.
NOTE: Install USB drivers prior to
making USB connection (see Section
5.1).
4) Powering Up
1. Apply power (PoE or 12VDC power source) to panel.
2. Verify panel power up.
•
The PoE or PWR LED will be illuminated and there
will be a slight delay as the operating system loads.
•
RUN LED will initially be solid red then
steadily flash green, once per second.
3. Verify panel and wiring functionality.
•
Trigger any input device. STS LED should flash
BLUE briefly.
•
Swipe a card at any reader. RDR LED should flash
GREEN briefly.
Note: For dry-type configurations, the power supply must be voltage-
compatible, listed to UL 294 or UL 609 for UL installations and
CAN/ULC-S318 for ULC installations, and able to supply sufficient
backup power.
CONGRATULATIONS!
YOU HAVE SUCCESSFULLY POWERED UP
the NetAXS-123 Access Controller!