Safety (Interlock) Card X102, X 103, X105; Appendix; Pin Assignment X110 - ferrotec genius Mounting Instructions

Evaporation controller
Table of Contents

Advertisement

Mounting instruction Genius
4 Relayoutpts 24 V/500 mA (momentarily 2 A) short circuit proof.
Output K1: B1 - B5
Output K2: B2 - B5
Output K3: B3 - B5
Output K4: B4 - B5
2 digital transistor outputs 24 V/500 mA (temporarily 2 A) short circuit proof.
Output T21: B6, PWM capable
Output T21: B7, can actuate a motor with output 5
6 optocoupled digital inputs (high = 8 V to 30 V, non polarity)
Input 1: A1 - A7
Input 2: A2 - A7
Input 3: A3 - A7
Input 4: A4 - A7
Input 5: A5 - A7
Input 6: A6 - A7
Electrically insulated voltage of 24 V/2 A and. +15 V/100 mA
9.4
Safety (Interlock ) Card X102, X 103, X105
Using
X102
the connection for the hand remote (X114) can be patched to the
front panel.
Using
X103
the connection for the RS-232 (X112) can be patched to the front
panel.
Using
X105
a safe switch can be integrated for the rotation of the pocket on a
multi pocket evaporator when the vacuum chamber is open. (The rotation is
only possible when an addition button is pressed.)
The pocket rotation is only possible if the contacts B2 A2 are supplied with 24
Volt DC. The voltage therefore is supplied on contact B1 and A1 and can be
guides through a so called safe switch. The status of the relay is given on the
contacts (normally open). If two evaporation controllers are used for co-evapor­
ation the connections are in parallel. Only one voltage supply is allowed to be
used.
Pin assignment
X105
+ 24 VDC
Relay Coil
Feedback status (normally
closed)
10

Appendix

10.1

Pin assignment X110

Pin assignment X110
PIN NO.
A1 - B1
A2 - B2
A3 - B3
A4 - B4
A5 - B5
A6 - B5
A7 - B7
Version 2.0.6
B 1
0 VDC
B 2
Relay Coil
Feedback status (normally
B 3
closed)
X110
Function
Input 1
Input 2
Input 3
Status chamber interlock* (1=ok)
Input 4
Input 5
Input 6
Output K1
53/78
A 1
A 2
A 3
Status water interlock (1=ok)
Status vacuum interlock (1=ok)
Status external interlock* (1=ok)
HV ON * (pos. slope)
HV OFF * (1=HV off)
relaycontact with B7;
Ferrotec GmbH
Fig. 21: Safety
interlock card

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for ferrotec genius

Table of Contents