Functions
2.1 General
Addr.
Parameter
142
Therm.Overload
143
TRANSFORMER
144
V-TRANSFORMER
145
P. INTERFACE 1
146
P. INTERFACE 2
147
NUMBER OF RELAY
148
GPS-SYNC.
149
charge I comp.
160
L-sections FL
2.1.2

General Power System Data (Power System Data 1)

The device requires some plant and power system data in order to be able to adapt its functions accordingly,
depending on the actual application. The data required include for instance rated data of the substation and the
measuring transformers, polarity and connection of the measured quantities, if necessary features of the circuit
breakers, and others. Furthermore, there are several function parameters associated with several functions
rather than one specific protection, control or monitoring function. The Power System Data 1 can only be
changed from a PC running DIGSI and are discussed in this section.

2.1.2.1 Setting Notes

Polarity of the current transformers
In address 201 CT Starpoint, the polarity of the wye-connected current transformers is specified (the fol-
lowing figure also goes for only two current transformers). The setting determines the measuring direction of
the device (forward = line direction). A change in this setting also results in a polarity reversal of the earth
current inputs I
44
Setting Options
Disabled
Enabled
NO
YES
Not connected
connected
Enabled
Disabled
IEEE C37.94
Disabled
Enabled
IEEE C37.94
2 relays
3 relays
4 relays
5 relays
6 relays
Enabled
Disabled
Enabled
Disabled
1 Section
2 Sections
3 Sections
or I
.
E
EE
Default Setting
Disabled
Thermal Overload Protection
NO
Transformer inside protection
zone
connected
Voltage transformers
Enabled
Protection Interface 1 (Port D)
Disabled
Protection Interface 2 (Port E)
2 relays
Number of relays
Disabled
GPS synchronization
Disabled
charging current compensation
1 Section
Line sections for fault locator
C53000-G1176-C169-5, Release date 02.2011