Siemens SIPROTEC Manual page 352

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Functions
2.18 Synchronism and Voltage Check (optional)
Figure 2-171
Synchro check logic
Operating modes
The closing check for automatic reclosing is possible in one of the following operating modes:
AR SYNC-CHECK
AR Usy1<Usy2>
AR Usy1>Usy2<
AR Usy1<Usy2<
AR OVERRIDE
352
Released at synchronism, that is when the critical values AR
maxVolt.Diff, AR maxFreq.Diff, AR maxAngleDiff are within the
set limits.
Released if measuring point Usy1< is de-energised and the measuring point
Usy2> is energised.
Released if measuring point Usy1> is energised and the measuring point
Usy2< is de-energised.
Released if measuring point Usy1< is de-energised and the measuring point
Usy2< is also de-energised.
Released without any check.
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011