Siemens SIPROTEC Manual page 69

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Addr.
Parameter
1124
center phase
1125
C0/C1
1126
RM/RL ParalLine
1127
XM/XL ParalLine
1128
RATIO Par. Comp
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1133A
T DELAY SOTF
1134
Line Closure
1135
Reset Trip CMD
1136
OpenPoleDetect.
1140A
I-CTsat. Thres.
1150A
SI Time Man.Cl
1151
SYN.MAN.CL
1152
Man.Clos. Imp.
1155
3pole coupling
1156A
Trip2phFlt
1161
VECTOR GROUP U
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
C
Setting Options
unknown/sym.
Phase 1
Phase 2
Phase 3
0.01 .. 10.00
0.00 .. 8.00
0.00 .. 8.00
50 .. 95 %
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
2 .. 70 V
0.01 .. 30.00 sec
0.05 .. 30.00 sec
only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
CurrentOpenPole
Current AND CB
Pickup Reset
OFF
Current AND CB
w/ measurement
1A
0.2 .. 50.0 A; ∞
5A
1.0 .. 250.0 A; ∞
0.01 .. 30.00 sec
with Sync-check
w/o Sync-check
NO
(Setting options depend
on configuration)
with PICKUP
with TRIP
3pole
1pole leading Ø
1pole lagging Ø
0 .. 11
Default Setting
unknown/sym.
center phase of feeder
0.75
Compensation factor
C0/C1
0.00
Mutual Parallel Line comp.
ratio RM/RL
0.00
Mutual Parallel Line comp.
ratio XM/XL
85 %
Neutral current RATIO
Parallel Line Comp
0.10 A
Pole Open Current
Threshold
0.50 A
30 V
Pole Open Voltage
Threshold
0.10 sec
Seal-in Time after ALL clo-
sures
0.25 sec
minimal time for line open
before SOTF
I or Man.Close
Recognition of Line Clo-
sures with
CurrentOpenPole
RESET of Trip Command
w/ measurement
open pole detector
20.0 A
CT Saturation Threshold
100.0 A
0.30 sec
Seal-in Time after
MANUAL closures
NO
Manual CLOSE
COMMAND generation
None
MANUAL Closure Impulse
after CONTROL
with TRIP
3 pole coupling
3pole
Trip type with 2phase
faults
0
Vector group numeral for
voltage
Functions
2.1 General
Comments
69