Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Functions
2.25 Function Control and Circuit Breaker Test
Figure 2-218
Logic diagram of the manual closing procedure
Reclosure via the integrated control functions - on-site control, control via DIGSI, control via serial interface -
can have the same effect as manual closure, see parameter 1152 Chapter 2.1.4.1 at margin heading „Circuit
Breaker Status".
If the device has an integrated automatic reclosure, the integrated manual closure logic of the 7SD5 automat-
ically distinguishes between an external control command via the binary input and an automatic reclosure by
the internal automatic reclosure so that the binary input „>Manual Close" can be connected directly to the
control circuit of the close coil of the circuit breaker (Figure 2-219). Each closing operation that is not initiated
by the internal automatic reclosure function is interpreted as a manual closure, even it has been initiated by a
control command from the device.
Figure 2-219
CB
TC
CBaux
444
Manual closure with internal automatic reclosure
Circuit breaker
Circuit breaker close coil
Circuit breaker auxiliary contact
SIPROTEC, 7SD5, Manual