Limit Value Monitoring; Setting Notes; Information List - Siemens SIPROTEC Manual

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Functions
2.26 Additional Functions

2.26.10.1Limit value monitoring

Set points can be set for the following measured and metered values:
• IL1dmd>: Exceeding a preset maximum average value in Phase L1.
• IL2dmd>: Exceeding a preset maximum average value in Phase L2.
• IL3dmd>: Exceeding a preset maximum average value in Phase L3.
• I1dmd>: Exceeding a preset maximum average value of the positive sequence system currents.
• |Pdmd|> : Exceeding a preset maximum average active power.
• |Qdmd|>: Exceeding a preset maximum average reactive power.
• |Sdmd|> : Exceeding a preset maximum average value of the apparent power.
• |cosϕ|< falling below a preset power factor.

2.26.10.2Setting Notes

Set Points for Measured Values
The settings are entered under MEASUREMENT in the sub-menu SET POINTS (MV) (MV) by overwriting the
existing values.

2.26.10.3Information List

No.
Information
-
IL1dmd>
-
IL2dmd>
-
IL3dmd>
-
I1dmd>
-
|Pdmd|>
-
|Qdmd|>
-
Sdmd>
-
PF<
273
SP. IL1 dmd>
274
SP. IL2 dmd>
275
SP. IL3 dmd>
276
SP. I1dmd>
277
SP. |Pdmd|>
278
SP. |Qdmd|>
279
SP. |Sdmd|>
285
cosϕ alarm
484
Type of In-
formation
LV
Upper setting limit for IL1dmd
LV
Upper setting limit for IL2dmd
LV
Upper setting limit for IL3dmd
LV
Upper setting limit for I1dmd
LV
Upper setting limit for Pdmd
LV
Upper setting limit for Qdmd
LV
Upper setting limit for Sdmd
LV
Lower setting limit for Power Factor
OUT
Set Point Phase L1 dmd>
OUT
Set Point Phase L2 dmd>
OUT
Set Point Phase L3 dmd>
OUT
Set Point positive sequence I1dmd>
OUT
Set Point |Pdmd|>
OUT
Set Point |Qdmd|>
OUT
Set Point |Sdmd|>
OUT
Power factor alarm
Comments
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011