Siemens SIPROTEC Manual page 345

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Addr.
Parameter
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Setting Options
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
YES
NO
0.01 .. 300.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
2.17 Automatic Reclosure Function (optional)
Default Setting
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR