Technical Data
4.1 General
DNP 3.0 FO
Ethernet electrical (EN 100)
for IEC 61850 and DIGSI
Ethernet optical (EN 100) for
IEC 61850 and DIGSI
The OLM converter requires an operating voltage of DC 24 V. If the operating voltage is > DC 24 V, the additional power
supply 7XV5810-0BA00 is required.
578
FO connector type
Connection for panel flush-mounting
housing
Connection for surface-mounting housing Please use version with DNP3.0 RS485 in the
Transmission rate
optical wavelength
Laser Class 1 according to EN60825-1/-2 when using glass fibre 50 μm / 125 µm or
Permissible optical signal attenuation
Transmission distance
Connection for panel flush-mounting
housing
Connection for surface-mounting housing at the bottom side of the console housing
Test voltage (regarding connector)
Transmission rate
Transmission distance
FO connector type
Connection for panel flush-mounting
housing
for surface-mounting housing
optical wavelength
Transmission rate
Laser class 1 acc. to
EN 60825-1/-2
Permissible optical signal attenuation
Transmission distance
ST connector transmitter/receiver
rear panel, slot „B"
console housing at the housing bottom as well
as a separate electrical/optical converter
up to 19 200 baud
λ = 820 nm
when using glass fibre 62.5 μm / 125 µm
max. 8 dB, with glass fibre 62.5 μm / 125 µm
max. 1.5 km
rear panel, slot „B"
2 x RJ45 female connector
100BaseT acc. to IEEE802.3
500 V; 50 Hz
100 Mbit/s
20 m
ST connector transmitter/receiver
rear panel, slot "B"
not available
λ = 1350 nm
100 Mbit/s
when using glass fibre 50 μm / 125 µm
or
when using glass fibre 62.5 μm / 125 µm
max. 5 dB, with glass fibre 62.5 μm / 125 µm
max. 800 m
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011