Siemens SIPROTEC Manual page 700

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Appendix
A.7 Settings
Addr.
Parameter
3501
FCT Synchronism
3502
Dead Volt. Thr.
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A
AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
3518
AR Usy1<Usy2<
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A
MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
3601
O/U FREQ. f1
3602
f1 PICKUP
3603
f1 PICKUP
3604
T f1
3611
O/U FREQ. f2
3612
f2 PICKUP
3613
f2 PICKUP
3614
T f2
3621
O/U FREQ. f3
3622
f3 PICKUP
3623
f3 PICKUP
3624
T f3
3631
O/U FREQ. f4
700
Function
C
Sync. Check
ON
OFF
ON:w/o CloseCmd
Sync. Check
1 .. 100 V
Sync. Check
20 .. 125 V
Sync. Check
20 .. 140 V
Sync. Check
0.01 .. 600.00 sec; ∞
Sync. Check
0.00 .. 30.00 sec
Sync. Check
(Setting options depend
on configuration)
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Setting Options
Default Setting
ON
5 V
90 V
110 V
1.00 sec
0.00 sec
None
w/o T-CB close
2.0 V
0.10 Hz
10 °
YES
NO
NO
NO
NO
w/o T-CB close
2.0 V
0.10 Hz
10 °
YES
NO
NO
NO
NO
ON: Alarm only
49.50 Hz
59.50 Hz
60.00 sec
ON: Alarm only
49.00 Hz
57.00 Hz
30.00 sec
ON: Alarm only
47.50 Hz
59.50 Hz
3.00 sec
ON: Alarm only
C53000-G1176-C169-5, Release date 02.2011
Comments
Synchronism and Voltage Check
function
Voltage threshold dead line / bus
Voltage threshold live line / bus
Maximum permissible voltage
Maximum duration of synchro-
nism-check
Synchronous condition stability
timer
Synchronizable circuit breaker
Operating mode with AR
Maximum voltage difference
Maximum frequency difference
Maximum angle difference
AR at Usy2>, Usy1>, and Synchr.
AR at Usy1< and Usy2>
AR at Usy1> and Usy2<
AR at Usy1< and Usy2<
Override of any check before AR
Operating mode with Man.Cl
Maximum voltage difference
Maximum frequency difference
Maximum angle difference
Manual Close at Usy2>, Usy1>,
and Synchr
Manual Close at Usy1< and
Usy2>
Manual Close at Usy1> and
Usy2<
Manual Close at Usy1< and
Usy2<
Override of any check before
Man.Cl
Over/Under Frequency Protec-
tion stage f1
f1 Pickup
f1 Pickup
T f1 Time Delay
Over/Under Frequency Protec-
tion stage f2
f2 Pickup
f2 Pickup
T f2 Time Delay
Over/Under Frequency Protec-
tion stage f3
f3 Pickup
f3 Pickup
T f3 Time Delay
Over/Under Frequency Protec-
tion stage f4
SIPROTEC, 7SD5, Manual