Table 8 - Wire Specifications for DC Power Terminal Block
Terminal
PanelView Plus 400, 600
PanelView Plus Compact 400, 600
700 to 1500 logic module
(1)
series A...D
700 to 1500 logic module
(1)
series E and later
PanelView Plus Compact 1000
PanelView Plus 6 terminals
series A or later
(1) Terminals with these logic modules support FactoryTalk View ME software, version 5.1 or earlier.
(2) Two-wire maximum per terminal.
PanelView Plus terminals with a 24V DC power input have these power ratings.
Table 7 - DC Power Ratings
Terminal
PanelView Plus 400 and 600
PanelView Plus Compact 400, 600
PanelView Plus 6 (700 to 1500)
PanelView Plus 700 to 1500
PanelView Plus Compact 1000
The power supply is internally protected against reverse polarity of the DC+ and
DC- connections. Connecting DC+ or DC- to the earth terminal may damage
the device.
Wire Type
Copper
Stranded
Cu 90 °C (194 °F)
or solid
Copper
Stranded
Cu 90 °C (194 °F)
or solid
Follow these steps to connect a PanelView Plus device to a DC power source.
WARNING: Explosion Hazard
Do not disconnect equipment unless power has been switched off and the
area is known to be nonhazardous.
Disconnect all power before installing or replacing components. Failure to
disconnect power may result in electrical shock or damage to the device.
1. Verify that the device is not connected to a power source.
2. Secure the DC power wires to the terminal block.
Make sure you connect the DC+ and DC- wires to the correct positions
on the power terminal block.
3. Secure the earth/ground wire.
• On the 400 and 600 terminals, secure the earth/ground wire to the
functional earth/ground terminal on the input power terminal block.
• On the 700 to 1500 terminals, secure the earth/ground wire to the
earth/ground terminal screw at the bottom of the display.
Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011
Wiring and Grounding Guidelines for PanelView Plus Terminals
Input Range
24V DC nom (18...30V DC)
25 W max (1.0 A at 24V DC)
24V DC nom (18...32V DC)
70 W max (2.9 A at 24V DC)
Dual-wire
Single-wire
(2)
Gauge
Gauge
2
0.3...1.3 mm
0.3...2.1 mm
22...16 AWG
22...14 AWG
2
0.3...1.3 mm
0.3...2.1 mm
22...16 AWG
22...14 AWG
Terminal Screw Torque
0.45...0.56 N•m
(4...5 lb•in)
2
0.23...0.34 N•m
(2...3 lb•in)
2
0.56 N•m (5 lb•in)