Tune For Simplex Outputs; Table 4-9 Procedure For Starting "Tune - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

4.10.1

Tune for Simplex Outputs

After "TUNE" has been enabled, you can start Accutune as shown in Table 4-9.
Step
1
2
3
4
5
6
ATTENTION
The Accutune process may be aborted at any time by changing the lower display back to "NoTUNE" or
by switching the controller into Manual Mode.
3/07

Table 4-9 Procedure for Starting "TUNE"

Operation
Configure LSP1
Switch to
"Automatic" Mode
Show Tuning
Prompt
Initiate Tuning
Tuning in operation
UDC3500 Universal Digital Controller Product Manual
Monitoring and Operating the Controller
Press
Until SP (Local Setpoint 1) shows
Lower
in the lower display.
Display
Until LSP1 is to the desired value.
or
Until the "A" indicator is lighted (on
Man/Auto
controllers with Manual option).
Until "TUNE OFF" is shown on
Lower
lower display.
Display
Select "DO SLOW" or "DO FAST"
in lower display.
Lower
Upper display will show a "T" as
Display
long as ACCUTUNE process is
operating. When process
completes, tuning parameters are
calculated and lower display will
show "NO TUNE" prompt.
Result
207