Communications; Table 10-29 Set-Up Group - Communications - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

10.7.20

Communications

Table 10-29 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Communications.
Parameter
Description
Shed Time
Shed Mode and
Output
Shed Setpoint
Recall
Computer Setpoint
Ratio
Computer Setpoint
Bias
Loop2 Computer
Setpoint Ratio
Loop2 Computer
Setpoint Bias
Communication
Address
Communications
Type
IR Port Enable
Baud Rate
Transmit Delay
3/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-29 Set-up Group – Communications
Register
Address
ID
Hex
Decimal
79
004F
79
162
00A2
162
163
00A3
163
90
005A
90
91
005B
91
90
015A
346
91
015B
347
77
004D
77
231
00E7
231
241
00F1
241
232
00E8
232
78
004E
78
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
INT
R/W
0 = No Shed
1 = 255 sample periods
INT
R/W
0 = Last Mode and Last
Output
1 = Manual Mode, Last
Output
2 = Manual Mode, Failsafe
Output
3 = Automatic Mode
INT
R/W
0 = To Last Local Setpoint
used
1 = CSP
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
FP
R/W
1 - 99
INT
R/W
0 = None
1 = Disable
2 = RS-485 Modbus
3 = Ethernet only if installed
INT
R/W
0 = Disable
1 = Enable
INT
R/W
0 = 4800
1 = 9600
2 = 19200
3 = 38400
FP
R/W
Response Delay in ms
(1 to 500) +6ms
Data Range or
Enumerated Selection