Modbus Read, Write and Override Parameters plus Exception Codes
10.2 Reading Control Data
Overview
The following control data can be read from this instrument:
•
Input 1
•
Input 2
•
Input 3
•
Input 4
•
Input 5
•
PV, SP, Output for each Loop
Register Addresses
Use the identifying codes listed in Table 10-1 to read the specific items.
A Write request for these codes will result in an Error message.
Parameter
Description
Input #1
123
Input #2
124
Input #3
126
Input #4
120
Input #5
121
PV, SP, Output
122
Loop 1
PV, SP, Output
122
Loop 2
PV Range Low
54
Loop1
PV Range High
55
Loop1
PV Range Low
54
Loop2
PV Range High
55
Loop2
350
Table 10-1 Control Data Parameters
Register
Address
ID
Hex
Decimal
007B
123
007C
124
007E
126
0078
120
0079
121
007A
122
017A
378
0036
054
0037
055
0136
310
0137
311
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
FP
RD
In Engineering Units or
Percentage
FP
RD
In Engineering Units or
Percentage
FP
RD
In Engineering Units or
Percentage
FP
RD
In Engineering Units or
Percentage
FP
RD
In Engineering Units or
Percentage
FP
RD
In Engineering Units
FP
RD
In Engineering Units
FP
RD
–999.0 to +9999
in Engineering Units
FP
RD
–999.0 to +9999
in Engineering Units
FP
RD
–999.0 to +9999
in Engineering Units
FP
RD
–999.0 to +9999
in Engineering Units
Data Range or
Enumerated Selection
3/07