Function Prompt
Lower Display
SHED SP
UNITS
CSP RATO
CSP BIAS
CSP2RATO
CSP2BIAS
3/07
Selections or
Range of Setting
Upper Display
TO MAN
FSAFE
TO AUTO
TO LSP
TO CSP
ENG
PERCENT
–20.0 to 20.0
–999. to 9999.
(engineering units)
–20.0 to 20.0
–999. to 9999.
(engineering units)
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
TO MAN—MANUAL MODE, SAME OUTPUT
The controller will return to manual mode at the
same output level that it had before shed.
FSAFE—MANUAL MODE, FAILSAFE OUTPUT
The controller will return to manual mode at the
output value selected at Control prompt FAILSAFE.
TO AUTO—AUTOMATIC MODE, LAST SP
The controller will return to the automatic mode and
the last setpoint used before shed.
SHED SETPOINT RECALL—The instrument will
control to the selected Setpoint following a Shed.
(controller switches from using CSP to LSP)
ATTENTION If SHEDENAB is configured for
DISABLE, then this prompt will not be configurable.
NOTE: if a RSP is the current setpoint, a CSP
override will not be used. CSP overrides local
setpoint only.
TO LSP—When a Shed occurs, the controller
switches from slave to monitor mode and uses the
last local setpoint prior to the slave mode. The CSP
value is disregarded on Shed.
TO CSP—When a SHED timeout occurs, the
controller switches from slave to monitor mode and
uses the local setpoint that is set equal to the CSP
value.
COMPUTER SETPOINT UNITS
ENG—Engineering units
PERCENT—Percent of PV range
COMPUTER SETPOINT RATIO—Computer
setpoint ratio for Loop 1.
COMPUTER SETPOINT BIAS—Computer setpoint
bias in Engineering Units for Loop 1.
LOOP 2 COMPUTER SETPOINT RATIO—
Computer setpoint ratio for Loop 2.
LOOP 2 COMPUTER SETPOINT BIAS—Computer
setpoint bias in Engineering Units for Loop 2.
Configuration
163