Honeywell UDC3500 Product Manual page 87

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Function Prompt
Lower Display
RECYCLES
HOTSTART
SEG1RAMP or
SEG1RATE
SEG1PID
SEG2 SP
SEG2TIME
SOAK2DEV
SEG2 PID
SEG3RAMP or
SEG3RATE
SEG3 PID
SEG4 SP
SEG4TIME
SOAK4DEV
SEG4 PID
SEG5RAMP or
SEG5RATE
SEG5 PID
SEG6 SP
SEG6TIME
SOAK6DEV
SEG6 PID
SEG7RAMP or
3/07
Selections or
Range of Setting
Upper Display
0 to 100 recycles
DISABLE
ENABLE
0-99 hours.0-59 minutes
Engineering units/minute
or
Engineering units/hour
1-4
Within the Setpoint limits
0-99 hours.0-59 minutes
0.000 to 99.99
1-4
Selections are same as
above.
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
Number of Program Recycles
HOT START—This feature allows the SP Program
to start at the current PV value rather than the
current Setpoint value.
ATTENTION Not used when linking programs.
Segment #1 Ramp Time or
Segment #1 Ramp Rate
ATTENTION This parameter is affected by the
RAMPUNIT configuration (see above). All ramps will
use the same selection.
PID Set Selection
ATTENTION The PID Set Selection prompts will
only show up when PID SETS in the Control 1 or
Control 2 Setup Group is set to 4 KEYBD.
Segment #2 Soak Setpoint Value
Segment #2 Soak Duration
Guaranteed Soak Deviation Value For Soak
Segment #2—The number selected will be the PV
value (in engineering units) above and below the
setpoint outside of which the Soak Segment timer
halts. A value of 0.000 is equivalent to no
Guaranteed Soak.
PID Set Selection—This selection is Loop
dependent.
ATTENTION The PID Set Selection prompts will
only show up when PID SETS in the Control 1 or
Control 2 Setup Group is set to 4 KEYBD.
Same as above
Configuration
71

Advertisement

Table of Contents
loading

Table of Contents