Algorithm; Table 10-17 Set-Up Group - Algorithm - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

10.7.8

Algorithm

Table 10-17 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Algorithm.
Parameter
Description
Control Algorithm
Selection
(Selection here
will affect ID code
160 in Output
Algorithms.)
Control Algorithm
Selection Loop2
PID Loops
Output Override
Timer
Period
Start (Initiation)
Time Display
(Selection)
Timer Reset
Timer Increment
3/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-17 Set-up Group – Algorithm
Register
Address
ID
Hex
Decimal
128
0080
128
128
0180
384
168
01A8
424
136
0188
392
216
00D8
216
99
0063
099
217
00D9
217
218
00DA
218
214
00D6
214
215
00D7
215
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = ON/OFF
1 = PID-A
2 = PID-B
3 = PD-A with Manual
Reset
4 = Three Position Step
5 = Disable
INT
R/W
0 = unused
1 = PID-A
2 = PID-B
3 = PD with Manual Reset
INT
R/W
0 = Loop 1 Only
1 = Loop 2 Enabled
2 = Loop 1 & 2 are
cascaded with Loop 2 as
primary (No Output) Loop
1 is secondary
INT
R/W
0 = Disabled
1 = Hi Select
2 = Lo Select
INT
R/W
0 = Disable
1 = Enable
FP
R/W
00.00 TO 99.59
INT
R/W
0 = Key (Run/Hold Key)
1 = Alarm 2
INT
R/W
0 = Time Remaining
1 = Elapsed Time
INT
R/W
0 = Key (Run/Hold Key)
1 = AL1 (Alarm 1 or Key)
INT
R/W
0 = Minutes (Counts
hr/minute)
1 = Sec (Counts min/sec)
Data Range or
387