Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Gate 1 InputA (B
LT A or B GT A)
Gate 1 InputB
(OR, NOR, AND,
NAND, X OR, X
NOR)
Gate 1 InputB (B
LT A or B GT A)
Logic Gate1 K
Constant
Gate 2 InputA
(OR, NOR, AND,
NAND, X OR, X
NOR)
396
Register
Address
ID
Hex
Decimal
171
40AB
16555
153
4099
16537
172
40AC
16556
100
4064
16484
156
409C
16540
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop1PV
6 = Loop1SP
7 = CONST K
8 = Loop 2 PV
9 = Loop 2 SP
INT
R/W
0 = Digital Input 1
1 = Digital Input 2
2 = Digital Input 3
3 = Digital Input 4
4 = Relay 1
5 = Relay 2
6 = Relay 3
7 = Relay 4
8 = Relay 5
9 = Gate Out 1
10 = Gate Out 2
11 = Gate Out 3
12 = Gate Out 4
13 = Gate Out 5
14 = FIX ON
15 = FIX OFF
16 = MA MODE
17 = LR SPL1
18 = ADAPT1
19 = MA MODE2
20 = LR SPL2
21 = ADAPT2
INT
R/W
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop1PV
6 = Loop1SP
7 = CONST K
8 = Loop 2 PV
9 = Loop 2 SP
INT
R/W
–999.0 to +9999
INT
R/W
Same as ID 152
Data Range or
3/07

Advertisement

Table of Contents
loading

Table of Contents