Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
ATTENTION
Changing the Input Type will result in the loss of Field Calibration values and will restore the
Factory Calibration values.
Input 2 Transmitter
Characterization
Input 2 High
Range Value
Input 2 Low Range
Value
Input 2 Ratio
Input 2 Bias
Input 2 Filter
Input 2 Emissivity
Input 2 Burnout
404
Register
Address
ID
Hex
Decimal
171
00AB
171
035
0023
035
036
0024
036
037
0025
037
038
0026
038
43
002B
043
44
002C
044
165
00A5
165
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
FP
R/W
–999. to 9999.
Engineering Units
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
0 to 120 seconds
FP
R/W
0.01 to 1.00
INT
R/W
0 = None
1 = Up
2 = Down
3 = No Failsafe
Data Range or
3/07