Configuration
Function Prompt
Lower Display
EU/HR UP
EU/HR DN
SP PROG
(optional feature)
SP Ramp must be
disabled for SP
Program prompts to
appear. If SP Rate is
enabled, it does not
operate while an SP
Program is running.
STRT SEG
END SEG
RAMPUNIT
RECYCLES
60
Selections or
Range of Setting
Upper Display
0 to 9999 in engineering
units per hour
0 to 9999 in engineering
units per hour
DISABLE
ENABLE
ENABLE2
ENABL12
1 to 20
2 to 20 even numbers
Always end in a soak
segment
(2, 4, ... 20)
TIME
EU/MIN
EU/HR
0 to 100 recycles
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
RATE UP—Rate up value. When making a setpoint
change, this is the rate at which the controller will
change from the original setpoint up to the new one.
The ramping (current) setpoint can be viewed as SPn
in the lower display.
Entering a 0 will imply an immediate step change in
Setpoint (i.e., no rate applies).
RATE DOWN—Rate down value. When making a
setpoint change, this is the rate at which the controller
will change from the original setpoint down to the new
one. The ramping (current) setpoint can be viewed as
SPn in the lower display.
Entering a 0 will imply an immediate step change in
Setpoint (i.e., no rate applies).
SETPOINT RAMP/SOAK PROGRAM #1—Available
only with controllers that contain this option.
SP RAMP must be disabled.
DISABLE—Disables all Setpoint Programs.
ENABLE—Setpoint Program runs on Loop 1.
ENABLE2—Setpoint Program runs on Loop 2.
ENABL12—Setpoint Program runs on both Loop1
and Loop 2.
ATTENTION SP Program #1 must be enabled in
order to use SP Programs 2, 3 and 4.
START SEGMENT NUMBER
END SEGMENT NUMBER
ATTENTION When SP Programs 1 and 2 are
linked, this parameter does not appear. The value is
automatically set to 20 and the End Segment Number
is controlled by the selection for End Segment in SP
Program #2.
RAMPUNIT—Engineering Units for Ramp Segments
TIME in hours: minutes
RATE in Engineering units per minute
RATE in Engineering units per hour
Number of Program Recycles
3/07