MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM

Analog Outputs

The WEB-EHSERIESNX26XX is equipped with four analog outputs (AOs).
In the event of an application stop (e.g., during application download), the analog outputs assume the safety
positions configured in WEBs N4.
The analog outputs can be configured in WEBs N4 as binary outputs (with an output of 0 V or 10 V, as the
case may be).

Binary Inputs / Pulse Counters

The WEB-EHSERIESNX26XX is equipped with four binary inputs (static dry-contact inputs) / pulse counters
(fast totalizers).
Criteria
Input type
Current rating (closed input)
Open contact voltage
Protection
Binary Input Specifications
The binary inputs of the CIPer Model 50 are static dry-contact inputs. This reduces the wiring effort, as it is
then not necessary to distribute an auxiliary voltage signal.
The polarity (normal = N.O. contact or reverse = N.C. contact) configuration defines if a logical 1 or a logical 0
is detected for a closed contact. This is done by selecting (in WEBs N4) one of the following options:
31-00233-02
Table 13. Specifications of AOs
Criteria
Output type
Max. output range
Min. resolution
Min. accuracy
Max. wire length
Wire cross section
Protection
Table 14. Specifications of BIs
Value
Binary input (static dry-contact) pulse counter (fast
totalizer)
2 mA
24 VDC
Against short-circuiting, 24 VAC
Open contact
≥ 3000 Ω (24 VDC on BI terminal)
Closed contact
≤ 500 Ω (short-circuit current: 2.0 mA)
Value
0...10 V (default)
2...10 V
0 ... 11 VDC (1 mA)
8 bit
± 150 mV
1200 ft
See Table 7
against short-circuiting, 24VAC
40