Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
ID
Input 4 Low
96
Range Value
Input 4 Ratio
97
Input 4 Bias
98
Input 4 Filter
94
Input 4 Burnout
133
408
Register
Address
Hex
Decimal
0060
96
0061
97
0062
98
005E
94
4085
16517
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
0 to 120 seconds
INT
R/W
0 = None
1 = Up
2 = Down
3 = No Failsafe
Data Range or